Operation
57
Liebert
®
 iCOM
®
Figure 47 Dehumidification and reheat control bands
The call for heating is based on the deviation between the dehumidification reheat setpoint 
(S132 right hand value) value of the selected sensor (S132 left hand value).
Return Sensor  is the default for all configurations and the only allowable setting when S102 
Temperature Control Sensor is set to “Return”. Supply Sensor  is selectable only when S102 
Temperature Control Sensor is set to “Supply.” Remote Sensor  is selectable only when  S102 
Temperature Control Sensor is set to either “Remote” or “Supply.” The reheat activation points are 
based on the dehumidification  temperature control band. Dehumidification temperature control band 
is established using these parameters:
• S132 (right hand value)
• S111 Heater Deadband
• + 1/2 (S13A-Dehum Reheat Prop Band)
• Dehumidification Temperature Control Band
Hot gas reheat or hot water reheat will start as shown in Figure 47, when the temperature decreases 
during the dehumidification process. Reheats operate only as proportional control. As the room 
temperature deviates further from setpoint on the dehumidification control band, the more reheats 
are activated.
Dehum Reheat Prop Band
-100%
-Temp
33%
33%
33%
Step 3
Step 2
Step 3 on
Step 3 off
Step 2 on
Step 2 off
Step 1 on
Step 1 off
0%
Dehum/ Reheat 
Setpoint
0%
Heater 
Deadband
Step 1
Dehum Reheat Prop Band
0%
Dehum/ Reheat 
Setpoint
-100 %
-Temp
33%
33%
33%
Step 3
Step 2
Step 3 on
Step 3 off
Step 2 on
Step 2 off
Step 1 on
Step 1 off
Step 1