Operation
Liebert
®
 iCOM
®
56
To avoid the dehumidification lockout:
• Increase the heat load for efficient operation
• Decrease S133 LL settings slightly
• Where applicable, decrease the reheat proportional band. This will allow the reheats to activate 
sooner, helping to prevent the low return condition.
Dehumidification Compressor Quantity
Under Factory Settings in the Advanced menu there is an item called Dehumidification With Comp. 
This will be set to either 1, 2, 1 or 2, or BOTH. This setting determines which compressors are used 
for dehumidification. It also determines if Low Limit 1 will be available and impacts how the reheats 
will operate during dehumidification. The Dehumidification With Comp field is set when the cooling 
unit is built and should not be adjusted without first consulting the factory. Table 9 outlines which 
Low Limit settings will be available, based on the Dehumidification With Comp selection.
Low Limit 1 and 2 will be available only on cooling units with two compressors when 
Dehumidification With Comp is set to BOTH.
Low Limit defines the sensor and the setpoint used to determine the low limit thresholds for all 
cooling and dehumidification modes.
The value of the selected sensor is compared with the setpoint set in S132 + the LL1 / LL2 settings 
(S133).
Possible selections are:
• 0 = Supply Sensor (selectable only when S102 Temperature Control Sensor is set to “Supply”)
• 1 = Remote Sensor (selectable only when S102 Temperature Control Sensor is set to either 
“Remote” or “Supply”)
Falls back to “Supply” when all Remote Sensors are set to “Disabled”
• 2 = Return Sensor - Default for all configurations, and the only allowable setting when S102 
Temperature Control Sensor is set to “Return.”
Defaults: Any time the S132 sensor setting changes (away from the default “Return” or back to 
“Return”), the setpoint will take the same value of what is set in S103 Temperature Setpoint.
Reheat During Dehumidification
The parameter Electric Reheat Operation in Service Menus>Options Setup defines how the heaters 
react if the temperature decreases during dehumidification. This parameter does not affect SCR 
reheat operation. The Electric Reheat Operation parameter is in the Advanced and should not be 
changed without factory approval.
No—No electric reheat allowed during dehumidification process.
Delayed—This setting applies only to two-compressor units with BOTH compressors selected for 
dehumidification. The electric reheats are prevented from turning On until Low Limit 1 is reached. At 
this condition, one stage of dehumidification is disabled and the reheats are activated. At 
Low Limit 2, both stages of dehumidification are disabled. When Delayed is selected on units with a 
single compressor selected for dehumidification (Dehumidification With Comp Setting: 1, 2, and 1 or 
2), the reheats will operate the same as they do for Staged as described below. Delayed is the default 
setting for Liebert DS units.
Staged—This setting applies to one or two compressor units. Electric heaters will stage as illustrated 
in Figure 47Staged is the default setting for Liebert Challenger 3000 units. On two-compressor 
units with Staged reheat selected and Dehumidification With Comp set to BOTH, the control allows 
operating two compressors and reheats simultaneously. The electrical service to the unit must be 
sized and wired for this option if selected.
Table 9
Dehumidification With Comp settings
Available to Set Value
Dehumidification With Comp Setting
Default Setting On
Low Limit 2 only
[blank] (units without compressors)
All Chilled Water Units
1 or 2 (Compressor 1 and 2 alternate)
Liebert DS
Low Limit 1 & 2
Both (both compressors dehumidify)