Emerson Liebert iCOM Manual De Usuario
Operation
55
Liebert
®
iCOM
®
Dehumidification Low Limit
Figure 46 Setpoints screen, page 3 of 9
Low Limit 1 and Low Limit 2 are used to avoid overcooling a room during dehumidification. When a
low limit is reached, a compressor or the liquid cooling source that is used for dehumidification is
disabled. It is re-enabled when the air temperature rises. The Low Limit 1 and 2 settings are in the
Service menu under Setpoints.
Low Limit 1: Low Limit 1 will disable one of two compressors for dehumidification. If only one
Low Limit 1: Low Limit 1 will disable one of two compressors for dehumidification. If only one
compressor is set for dehumidification, or if the dehumidification source is chilled water, this limit
will not be visible and will be inactive.
Low Limit 2: Low Limit 2 will disable both compressors for dehumidification. This limit will also
Low Limit 2: Low Limit 2 will disable both compressors for dehumidification. This limit will also
stop dehumidification in single compressor units and in chilled water units.
The limits become active when the air temperature drops below a temperature value equal to the sum
The limits become active when the air temperature drops below a temperature value equal to the sum
of the dehumidification reheat setpoint plus the value set on Low Limit 1 and 2 (the Low Limit
settings are negative values).The air temperature used for low limit is the same sensor used for
controlling reheat during dehumidification (left hand value on line S132).
A dehumidification source is deactivated if the return air temperature drops below the Deactivation
A dehumidification source is deactivated if the return air temperature drops below the Deactivation
Temperature, as in this example:
Dehumidification will not reactivate until:
• the air temperature is above S132 Dehumidification Reheat Setpoint
OR
• at least one compressor is in a call for cooling, at least 10 minutes has elapsed since
dehumidification was stopped and the Low Limit Sensor (S132) is greater than the Low Limit 2
(LL2) border.
NOTE
When the unit is in relative humidity control, only the right side of the menu is displayed and
When the unit is in relative humidity control, only the right side of the menu is displayed and
dew point will display the left side of the menu.
S132 Dehumidification
Temperature Setpoint:
70°F (21.1°C)
Low Limit Value:
-7°F (-3.8°C)
Deactivation Temperature:
63°F (17.2°C)
NOTE
If a cooling unit is equipped with SCR reheat and the SCR Control Type parameter is set to
If a cooling unit is equipped with SCR reheat and the SCR Control Type parameter is set to
Tight mode, then Low Limit 2 will be ignored, see 3.6 - Temperature Control—Reheat.