Operation
Liebert
®
 iCOM
®
70
3.10.1 High- and Low-Temperature and Humidity Events
High- and low-temperature and humidity alarms can be set for both the internal and optional 
external sensors. If a sensor reading exceeds a preset threshold, a warning will appear. These 
warnings are ignored after unit startup for a minimum of 1 minute. To increase the delay to warn, see 
3.10 - Event Types and Properties. The threshold settings are located in both the User and Service 
menus under Set Alarms. 
To apply threshold limits on the internal cooling unit sensors, the Return Sensor Alarms must be 
enabled. The high and low temperature and humidity internal sensor thresholds can then be set. To 
apply threshold limits on the optional external sensors, the Sensor A alarms must be enabled. The 
high and low temperature and humidity external sensor thresholds can then be set. If no external 
sensors are connected to the unit, it is recommended that the Sensor A Alarms be disabled.
FC LOCKOUT
2 Sec
2 sec / 0 – 9999 *
WRN
COMPRESSOR(S) LOCKOUT
2 Sec
2 sec / 0 – 9999 *
WRN
COMP 1 SHORT CYCLE
0 Sec
0 - 9999
MSG
COMP 2 SHORT CYCLE
0 Sec
0 - 9999
MSG
No Power
0
0 seconds / 0-9999
WRN
Condensate 1 Failure
0
5 seconds / 0-9999
WRN
Condensate 2 Failure
0
5 seconds / 0-9999
WRN
EC Fan Fault
0
10 seconds / 0-9999
ALM
HIGH SUP TEMP
0
30 seconds / 0-9999
WRN
LOW SUP TEMP
0
30 seconds / 0-9999
ALM
REDUCED ECO AIRFLOW
0
3 seconds / 0-9999
WRN
ECO HI TEMP OVERRIDE
0
10 seconds / 0-9999
WRN
TEMP CTRL SENSOR FAIL
0
3 seconds / 0-9999
ALM
HIGH DEW POINT
0
30 seconds / 0-9999
WRN
LOW DEW POINT
0
30 seconds / 0-9999
WRN
HI DEW POINT SENSOR A
0
30 seconds / 0-9999
WRN
LOW DEW POINT SENSOR A
0
30 seconds / 0-9999
WRN
HIGH REMOTE SENSOR
0
30 seconds / 0-9999
WRN
POWER “A” FAILURE
0
10 seconds / 0-9999
ALM
POWER “B” FAILURE
0
10 seconds / 0-9999
ALM
AIRFLOW SENSOR FAILURE
0
10 seconds / 0-9999
WRN
HUM CTRL SENSOR FAIL
0
30 seconds / 0-9999
WRN
LOSS OF FLOW 
0
5 seconds / 0-9999
ALM
STAT PRES SENSOR FAIL
0
120 seconds / 0-9999
ALM
LOW STATIC PRESSURE
0
120 seconds / 0-9999
WRN
HIGH STATIC PRESSURE
0
120 seconds / 0-9999
WRN
STATPRES OUT OF RANGE
0
150 seconds / 0-9999
WRN
DAMPER FAILURE
0
10 seconds / 0-9999
ALM
BMS DISCONNECTED
0
ENABLED / DIS - ENAB
WRN
NOTE
The event messages will automatically reset if the temperature/humidity stays 1.8°F 
(1°C)/ 2% RH below or above the threshold for one minute.
Table 11
Possible event settings—some events not available in all units (continued)
Event
Internal Delay
(Before Action Occurs)
Default Delay / Selectable
(Before Action Occurs)
Type
(default)