Operation
Liebert
®
 iCOM
®
72
3.10.3 Analog Inputs
The Liebert iCOM allows an external sensor or analog device to be connected, scaled and viewed on the 
Liebert iCOM large display. These external devices require optional analog input connections that can be 
installed on new units at the factory or added to existing units in the field. The option provides the electrical 
connection from the Liebert iCOM control board to the required factory-supplied plug, harness and terminal 
strip. For parts, contact Liebert Services at (800) 800-543-2778. If a unit is equipped with this option, then a 
0-10VDC, 0-5VDC, 4-20mA, or a device such as a sensor or a damper can be connected to terminals 41 and 42, 
43 and 44, 45 and 46 or 47 and 48. See Table 13 for analog input availability.
Follow the settings in Figure 62 and Table 14 to set the input type based on the sensor output used. 
The default analog input is 0-5VDC. Only properly trained and qualified service technicians should 
change the analog input type.
Figure 62 Analog connection control board switch
COND 1 FAIL
Event Only
COND 2 FAIL
Event Only
D-SCROLL RED
Event + Reduces the Requested Compressor Capacity by 20%
SWAP VALVE
No Event -Active X Valve Closes and Y Opens / Inactive Y Closes 
and X Opens
EC FAN FAULT
Event + Sets Analog Output to 10V
ECO AIRFLOW
Event + Reduces Liebert Air Economizer Airflow
DAMPERSWITCH Damper + End Switch
POWER A
Event Only
POWER B
Event Only
Table 13
Number of analog inputs
Unit Type 
Number of Analog Inputs
Liebert CW
 with MBV
4; 2 may be used for valve feedback
Liebert CW with 3P (Floating Point Actuator)
4; 2 may be used for valve feedback
Liebert DS
 Air-Cooled
2; 2 used for low-pressure transducers
Liebert DS Water/Glycol Cooling
0; models without high-pressure transducers may have two
Liebert Challenger 3000
 Air-Cooled
3; one used for low-pressure transducers
Liebert Challenger 3000 Water/Glycol Cooled
2; one used for a low pressure transducer and a second 
potentially for a high-pressure transducer
NOTE
The analog inputs must be configured with the large display. The small display 
can only view them.
Table 12
Customer inputs (continued)
Setting
Reaction
On
Off
Switch Position
Switches #9 and #10 not 
applicable to Liebert CW
 
or to Liebert DS