Operation
71
Liebert
®
 iCOM
®
3.10.2 User Inputs
The user can connect and specify up to four custom alarm inputs, also known as remote alarm devices 
(RAD), depending on unit configuration. Two optional customer inputs are available on some cooling 
units. The optional inputs are not available on units equipped with low-pressure switches on Liebert 
DX equipment. Low-pressure transducers may be field-installed in lieu of low pressure switches if 
additional customer inputs are desired. 
Each input can be programmed to provide information about an event associated with the unit or 
space.
Each standard inputs is wired to Terminal 24 through a dry contact to locations 50, 51, 55 and 56, 
respectively, for Alarms 1 through 4 (see the unit’s electric schematic and installation manual 
terminal location).
The customer input configuration settings are in the Service menu under Set Alarms, Screen 3 of 11. 
The choices for the customer inputs are shown in Table 12 along with their associated reaction. The 
customer inputs can be programmed as normally open or normally closed to alarm.
NOTE
To enabled/disabled, delay activation and set event type (alarm, warn, message) see Event 
Types on page 68.
Table 12
Customer inputs
Setting
Reaction
Smoke
Event Only
Water Alarm
Event Only
C PMP Alarm
Event Only
Flow Alarm
Event Only
Stdby G Pmp
Event Only
Stdby Unit
Event Only
C-Input 1
Event Only
C-Input 2
Event Only
C-Input 3
Event Only
C-Input 4
Event Only
Rht Lockout
Event + Electrical Heaters Disabled
Hum Lockout
Event + Humidifier Disabled
Rht+Hum Lock
Event + Electrical Heaters and Humidifier Disabled
Comp Lockout
Event + Compressor(s) Disabled w/o Pump Down
Call Service
Event Only
High Temp
Event Only
Air Loss
Event Only
FC Lockout
Event + Free-Cooling Disabled
Heater Alarm
Event + Heaters Off
Flow AL SD
Event + Shut Down the Unit
Flow AL LC
Event + Lockout Compressors, No Pump Down (enabled only if at 
least one compressor is On; auto-reset depends on input status)
Comp Lock PD
Event + Compressor(s) Disabled w/ Pump Down
Enable FC
Forces Free-Cooling to On
HTRJ VFD
Activates the HEAT REJ VFD ALARM; no other function
HTRJ SPD
Activates the HEAT REJ SPD ALARM; no other function
FIRE ALARM
Event + Shuts the Unit Down
2
ND
 SETPOINT
No Event But Switches To The Second Setpoint
NO POWER
Event + Disables Unit
LSI
Event + Activates Humidifier Problem Alarm and Stop Filling 
Bottle When Full