Table 2: Common Chimney Problems - 
continued
 
Key Trouble  Diagnostic  Remedy 
Smoke pipe 
extends into 
chimney. 
Measurement 
of pipe from 
within or 
observation of 
pipe by means 
of a lowered 
light. 
Length of pipe 
must be 
reduced to 
allow end of 
pipe to be flush 
with inside of 
tile. 
Failure to 
extend the 
length of flue 
partition to the 
floor. 
By inspection 
or smoke test. 
Extend partition 
to floor level. 
Loose-fitted 
clean-out door. 
Smoke test. 
Close all leaks 
with cement. 
 
NOTE:  This furnace is approved for use with L-Vent
 
NOTE: Maximum temperature for L-Vent is 575°F 
(300°C). 
 
 
Table 4:  Min. Chimney Base Temperatures (°F) 
Chimney Height (ft.) 
Model 
11 20 28  36 
Chimneys with Thermal Resistance less than R6 
80F (060) 
300 
400 
535 
725 
80F (070) 
275 
340 
430 
535 
80F (080) 
270 
330 
405 
505 
120F (090) 
260 
320 
380 
475 
120F (100) 
250 
300 
355 
430 
120F (120) 
225 
300 
365 
430 
Chimney Height (ft.) 
Model 
11 20 28  36 
Chimneys with Thermal Resistance greater than R6 
80F (060) 
185 
200 
220 
250 
80F (070) 
175 
185 
205 
220 
80F (080) 
175 
185 
195 
215 
120F (090) 
175 
185 
195 
210 
120F (100) 
165 
185 
195 
205 
120F (120) 
165 
185 
195 
205 
 
IMPORTANT: The chimney must be capable of providing 
sufficient draft at all times for the safe removal of the 
products of combustion. 
 
The chimney should be tested under “winter” conditions; 
doors and windows closed, all other fossil fuel burning 
appliances on, clothes dryer on, bathroom fans on, etc. If 
the chimney cannot overcome the competition for air, it 
will be necessary to access the reason for it, and take 
corrective action. If the chimney is found to be sized 
correctly and in good repair, it will probably be necessary 
to re-evaluate the availability of combustion and 
ventilation air, and take corrective action. 
 
The flue pipe should be as short as possible with 
horizontal pipes sloping upward toward the chimney at a 
rate of one quarter inch to the foot. The flue pipe should 
not be smaller in cross sectional area than the flue collar 
on the furnace. The flue pipe should connect to the 
chimney such that the flue pipe extends into, and 
terminates flush with the inside surface of the chimney 
liner. Seal the joint between the pipe and the lining. The 
chimney outlet should be at least two feet above the 
highest point of a peaked roof. All unused chimney 
openings should be closed. Chimneys must conform to 
local, provincial or state codes, or in the absence of local 
regulations, to the requirements of the National Building 
Code. 
 
See Figure 2 and Table 3 for common chimney problems 
and their remedies. 
 
 
THE FURNACE MUST BE CONNECTED TO A FLUE 
HAVING SUFFICIENT DRAFT AT ALL TIMES TO 
ENSURE SAFE AND PROPER OPERATION OF THE 
APPLIANCE. 
The flue pipe must not be routed through concealed 
space, because it must be visually checked for signs of 
deterioration during the annual inspection and servicing. 
The flue pipe must not pass through any floor or ceiling, 
but may pass through a wall where suitable fire protection 
provisions have been installed. Refer to the latest edition 
of CAN/CSA B139 for rules governing the installation of 
oil burning equipment. In the United States, refer to the 
latest edition of NFPA 31 for regulations governing the 
installation of oil burning equipment. 
7.  BAROMETRIC DAMPER CONTROL 
This device is used in conjunction with conventional 
chimney venting. This control (or draft regulator) 
automatically maintains a constant negative pressure in 
the furnace to obtain maximum efficiency. It ensures that 
proper pressures are not exceeded. If the chimney does 
not develop sufficient draft, the draft control cannot 
function properly. The draft regulator, must be installed 
within the same room or enclosure as the furnace, and 
should not interfere with the combustion air supplied to 
the burner. The control should be located a minimum of 3 
flue pipe diameters from the furnace breeching and