F-2200 Series Vortex Flow Meter Installation and Operation Guide • Revised 12/08
1.4  ADDITIONAL REQUIRED MATERIALS
 
Installer is responsible for providing suitable fl anges and fasteners to connect the meter to the 
 
process piping. In addition, most installations will also require one reducer, one expander, pipe 
 
supports and a suffi cient length of straight pipe (pipe diameter = meter size) to meet the installation 
 
requirements outlined in this manual. Use of an optional fl ow rectifi er may be required in cases 
 
where the available space is not suffi cient to allow for proper upstream straight pipe run. 
1.5 WORKING 
ENVIRONMENT
 
ONICON F-2000 series vortex fl ow meters are designed for use in industrial environments that are 
 
free of corrosive liquids, fumes and excessive vibration. Do not expose the fl ow meter electronics 
 
enclosure to direct sunlight. Install a sunshade if necessary. Do not expose the fl ow meter to intense 
 
vibration. If necessary, provide additional support to the pipeline, at the meter location, to minimize 
 
vibration. The rotating design of the electronics enclosure makes it easier to connect the power and 
 
signal cables to the terminals in the rear of the enclosure. Rotate the enclosures as necessary before 
 
installing the meter.  
 
The ambient operating temperature range is 0° to 132° F.  
1.6 SERIAL 
NUMBER
 
The serial number for your F-2000 series vortex fl ow meter is located on the metal identifi cation 
 
plate mounted on the side of the electronics enclosure. Please have this number available whenever 
 
you contact ONICON for assistance.