ELECTRICAL DATA
Be sure that your outlet matches the appropriate 
blade configuration of the supplied plug and that it is 
within reach of the service cord. A hardwire kit is 
available as an accessory to change cord-connected 
units to hardwired units. (See Accessories table on 
page 14.)
ALL UNITS
■  
WIRE SIZE — Use recommended wire size given in 
Table 1 and install a single branch circuit. All wiring 
must comply with local and national codes. All units 
are designed to operate off single branch cir-
cuits only
.
NOTE: Use copper conductors only.
■  
GROUNDING — For safety and protection, the unit 
is grounded through the service cord plug or through 
separate ground wire provided on hardwired units. Be 
sure that the branch circuit or general purpose outlet 
is grounded.
TABLE 1 — SUGGESTED BRANCH CIRCUIT
WIRE SIZES*
LEGEND
AWG — American Wire Gage
*Single circuit from main box.
†Based on copper wire at 60 C temperature rating.
VOLTAGE SUPPLY
Check voltage supply at outlet. For satisfactory re-
sults, the voltage range must always be within the 
ranges found on the data information plate
(Figure 1).
■  
CORD-CONNECTED UNITS — The 250-v field-
supplied outlet must match the plug for the standard 
208/230-v units and be within reach of the service 
cord. The standard cord-connected 265-v units require 
an accessory electrical subbase for operation. See 
Accessories table, page 14, for subbase selection. Refer 
to Table 2 for proper receptacle and fuse type.
TABLE 2 — RECEPTACLES AND FUSE TYPES — 250,265 VOLTS
LEGEND
HACR — Heating, Air Conditioning, Refrigeration 
*May be used for 15-amp applications if fused for 15 amp.
ELECTRICAL SHOCK HAZARD
DO NOT alter cord or plug, and DO NOT use an 
extension cord. Personal injury or damage to the 
unit may result.
IMPORTANT: All standard cord-connected 265-v 
units will require a field-installed electrical sub-
base accessory.
NAMEPLATE AMPS
AWG WIRE SIZE†
7.0 to 12
14
12.1 to 16
12
16.1 to 24
10
RECEPTACLE
15 Amps
20 Amps
30 Amps
15 Amps
20 Amps
30 Amps
RATED VOLTS
250
250
250
265
265
265
TIME-DELAY TYPE
FUSE  (or HACR Circuit Breaker)
15
20*
30
15
20
30