SPECIAL APPLICATION
400-0384-003
29
8.3  INPUT PORTS DO NOT RESPOND
Cause 1:
The input pin is not grounded.
Solution:
Short the input port to ground using 
a switch or jumper and send the 
command [RDI*]. The status of all 
input ports will be displayed. A ‘1’ is 
for  on (shorted) and a ‘0’ is for off. 
Verify the grounded input  reads ‘1’. 
If all the ports show a high, ‘1’, call 
ALTINEX at (714) 990-2300. 
Otherwise, see Cause 2.
Cause 2:
The input is incorrectly programmed.
Solution:
If the PE1005 is seeing a high-to-low 
transition and there is no response, 
the setup may be wrong. Send the 
command [RDIN*] and note the 
subroutine  number assigned to the 
port. Then read the subroutine with 
the [RDS] command and verify the 
contents. If everything looks good
there may be a problem with the 
PE1005 operation, call ALTINEX at 
(714) 990-2300.