Bradford-White Corp BWCV Manual De Usuario

Descargar
Página de 44
Internet Version for Reference Only
 
Bradford White
Page 28
Copper Brute II
Page 29
The heater target temperature is set using the 
BOIL TARGET item in the Adjust menu. 
Note: External demand is not required in this 
mode of operation.
Tank Differential – A differential setting that 
operates 1⁄2 above and below the TANK TARGET is 
selectable using the TANK DIFF item in the Adjust 
menu.
6.3.9  Outdoor Reset Operation
When either mode 4 or 5 is selected, the control 
uses outdoor reset to control the water temperature. 
Outdoor reset adjusts the target temperature based 
on the outdoor air temperature and reset ratio. The 
reset ratio is determined from the Boiler Start, Boiler 
Design, Outdoor Start and Outdoor Design settings.
Heat Demand – For “heat demand” to exist, 
there must be continuity between the Com D (common 
demand) and the Ht D (heat demand) terminals. The 
heater ships with a jumper between these terminals. 
The control also evaluates the sensor(s) installed 
in the system. If the control is not in warm weather 
shutdown (WWSD), and the sensor(s) are below the 
target temperature, the Dem segment is turned on 
in the display. The control energizes the pump (on 
pump mounted boilers) and energizes the Pmp-Pmp 
terminals, and the heater pump segment is turned on 
in the display. The control then operates the stages to 
maintain the set point temperature.
Boiler Start (BOIL START) – The BOIL 
START temperature is the theoretical boiler supply 
water temperature that the heating system requires 
when the outdoor air temperature equals the OUTDR 
START temperature setting. The BOIL START is 
typically set to the desired building temperature (see 
Figure 15). 
Outdoor Start (OUTDR START) – The 
OUTDR START temperature is the outdoor air 
temperature at which the control provides the BOIL 
START water temperature to the system. The OUTDR 
START is typically set to the desired building 
temperature.
Outdoor Design (OUTDR DSGN) – The 
OUTDR DSGN is the outdoor air temperature that is 
the typical coldest temperature of the year where the 
building is located. This temperature is used when 
doing heat loss calculations for the building.
Boiler Design (BOIL DSGN) – The BOIL 
DSGN temperature is the water temperature required 
to heat the boiler zones when the outdoor air is as cold 
as the OUTDR DSGN temperature.
Warm Weather Shut Down (WWSD) – When 
the outdoor air temperature rises above the WWSD 
setting, the control turns on the WWSD segment 
in the display. When the control is in WWSD, the 
Dem segment is displayed if there is a heat demand. 
However, the control does not operate the heating 
system to satisfy this demand. The control does 
respond to a set point demand and operates as 
described in the Reset Override section (next).
Reset Override (SET POINT DEMAND) 
– This is used when override of the outdoor reset curve 
is needed, such as when an indirect water heater is 
served by the heating system. A set point demand is 
required whenever heat is required for the set point 
load. The set point demand overrides the reset water 
temperature. The control turns on the Setp Dem 
pointer in the display. The control energizes the pump 
(on pump-mounted heaters), energizes the Pmp-Pmp 
terminals, and turns on the heater pump segment in the 
display. The control then operates the heater stages to 
maintain the programmed target temperature. The reset 
override operation is not affected by WWSD.
6.3.10 External Heater Operation
When mode 6 is selected, the control allows for 
an external control to operate the heater’s stages. In 
this mode, the control operates the pump in order to 
provide purging and exercising. The staging operation 
is provided by an external device such as an Energy 
Management System (EMS) or External Staging 
Control.
Heat Demand – A heat demand is generated 
when stage one is wired properly, and the external 
control closes the contacts on the stage one terminals 
(1C-1NO), calling the heater for heat. The heater is 
shipped with a jumper between the Com D and Ht D 
terminals, and this jumper must remain in place when 
and external control is providing the heat demand 
Figure 15. Temperature Control Outdoor Start Graph.