Bradford-White Corp BWCV Manual De Usuario

Descargar
Página de 44
Internet Version for Reference Only
 
Bradford White
Page 28
Copper Brute II
Page 29
signal to these terminals. The control energizes the 
heater pump (if equipped), energizes the Pmp-Pmp 
terminals, and turns on the heater pump segment in the 
display. The control also turns on stage 1 of the heater. 
Section 5.3 contains important information about 
external staging controls and building automation 
systems. Other wiring methods may be unsafe. The 
wiring in Section 5.3 of this manual must be used.
6.3.11 Limit Controls
In addition to the temperature control, Copper 
Brute II appliances are fitted with a manual reset 
high limit and an automatic reset high limit. These 
are located near the rear of the cabinet on the right 
side, behind the slide out drawer (see Figure 17). 
Both controls should be set at least 25°F higher than 
the target temperature to avoid short cycling. To set 
these controls, remove the control panel cover and 
pull the control panel out to gain access. Appliances 
with reversed heat exchangers have the limit controls 
relocated to the left side of the appliance. The left 
access door must be removed to gain access to the 
limit controls on these appliances.
6.3.12 Advanced Programming Mode
Advanced programming mode allows the 
installer to set the temperature control for proportional 
staging. In advanced programming mode, the 
interstage differential, interstage delay, interstage on 
and off delay, and minimum time on and off are all set 
manually.
NOTE: Advanced programming mode is rarely 
required. It is intended for advanced installers, 
and only when the application demands such 
programming.
To enter advanced programming mode, remove 
the bezel on the temperature control by pulling out at 
the bottom. Remove the small Phillips head screw to 
access the dip switch. The dip switch is mounted on a 
circuit board. 
Locate the letter “A” on the circuit board and 
slide the corresponding dip switch toward the letter 
“A”. The default setting of this dip switch is toward 
the “OFF” lettering on the circuit board.
6.4  Operating the Burner and Set Up
6.4.1  Set Up for 0 to 2500 Feet Altitude
The Copper Brute II appliance utilizes a modular 
design to achieve its stage-firing. The setup must be 
checked before the unit is put in operation. Problems 
such as failure to start, rough ignition, strong exhaust 
odors, etc. can be due to improper setup. Damage to 
the Copper Brute II resulting from improper setup is 
not covered by the limited warranty.
1.      Using this manual, make sure the installation 
is complete and fully in compliance with the 
instructions.
2.      Determine that the appliance and system are 
filled with water and all air has been bled from 
both. Open all valves.
3.      Observe all warnings on the Operating 
Instructions label and turn on gas and electrical 
power to appliance.
4.      Switch on the heater power switch located on the 
right side of the unit.
5.      The heater will enter the start sequence, as long 
as the unit is being called for heat. The blower 
and pump come on for pre-purge, then the ignitor 
warm-up sequence starts and after the ignitor 
warm-up is complete and all safety devices are 
verified, the gas valves open. If ignition doesn’t 
occur, check that there is proper gas supply. 
Wait 5 minutes and start the unit again. During 
initial start up, air in the gas line may cause the 
heater to "lock out" during the first few trials 
for ignition. Depending on the ignition modules 
installed, the manual reset button on the ignition 
modules may need to be depressed to restart the 
heater.
6.      When the unit is running, the supply gas pressure 
must be checked. Inlet gas pressure must not 
exceed 13" W.C. (3.2kPa). The minimum inlet 
gas pressure is 5" W.C. (1.2kPa).
7.      Once the inlet gas pressure is verified, the 
outlet gas pressure from each valve (manifold 
gas pressure) must be checked, and adjusted, if 
necessary. The manifold gas pressure must be 
2.5" W.C. (0.62kPa).
8.      Complete the setup by checking the CO
2
 at the 
outlet of the unit. The CO
2
 should be 8% for 
natural gas, or 9.2% for propane.
9.      After placing the heater in operation, the 
Burner Safety Shutoff Device must be tested
To test: 
         (a)    Close gas shutoff valve with burner 
operating.
         (b)    The flame will go out and blower will 
continue to run for the post purge cycle. 
One additional attempt to light will follow. 
Ignition will not occur as the gas is off. The 
ignition control will lockout, and will have 
to be reset before the unit will operate.
         (c)    Open gas shutoff valve. Restart the 
appliance. The ignition sequence will 
start again and the burner will start. The 
appliance will return to its previous mode 
of operation.
NOTE: Models 1000 - 2000 have two ignition controls 
and two ignitors, which work independently of one 
another. If the ignition control for stages 1 and 2 fails 
to properly light the main burners for those stages, the 
second ignition control will still be active, and will be 
able to energize stages 3 and 4. This, of course, will 
only occur if all other safety devices confirm that the 
unit will run in a safe condition.