Bradford-White Corp BWCV Manual De Usuario

Descargar
Página de 44
Internet Version for Reference Only
 
Bradford White
Page 30
Copper Brute II
Page 31
6.4.2  High  Altitude  Adjustment  and  Set 
Up
Copper Brute II appliances may be operated at 
high altitude (7700 ft., 2347 m) with a reduction in 
output of approximately 10%. At altitudes of less than 
or more than 7700 ft. (2347 m) the appliance will 
perform equally as well, but with differing reductions 
in output. At elevations higher than 7700 ft. (2347 
m) the reduction in output will exceed 10% and at 
elevations below 7700 ft. (2347 m) it will be less than 
10%. High altitude adjustment must not be made on 
appliances operating at elevations below 2500 ft. (762 
m).
No orifice changes are required to adjust the 
Copper Brute II appliances for high altitude. High 
altitude adjustment is accomplished by adjustment of 
the gas valve manifold pressure and the air shutter(s). 
The required instruments used to assist in these 
adjustments are a CO
2
 or O
2
 Analyzer and a U-Tube 
Manometer or other device capable of reading a 
pressure of 2.5-3.0 inches W.C. (0.62-0.75 kPa).
Start the adjustment process by checking the 
CO2 in the “as installed” condition. Adjust the air 
shutter(s) so that the CO
2
 is about 8% or the O
2
 is 
about 6.8% for appliances operating on Natural Gas. 
For appliances operating on LP Gas adjust the air 
shutter(s) so that the CO
2
 is about 9.2% or the O
2
 is 
about 6.8%. Appliances with two blowers should be 
adjusted so that the air shutters below each blower are 
open the same amount.
Once the CO
2
 or O
2
 has been set, the manifold 
pressure may be adjusted. Remove the 1/8 NPT plug 
from the lower side of the gas valve that is to be set 
and install a fitting, hose and manometer. Start the 
appliance and observe the manifold pressure. Manifold 
pressure must be adjusted to 3.0 in. W.C. (0.75 kPa) 
(for high altitude only, standard operating pressure is 
2.5 in. W.C. (0.62 kPa)). It is adjusted by removing the 
slotted cap on the gas valve and turning the adjustment 
screw (beneath the cap) clockwise to increase 
pressure and replaced after the adjustments have been 
completed and the fitting, hose and manometer have 
been removed and the 1/8" plug has been replaced. 
Repeat this process until all gas valves have been set. 
Note: The pressure can be set only when the appliance 
is operating and only when the particular gas valve 
being adjusted is energized by a call for heat from the 
staging control.
After all of the gas valve manifold pressures 
have been set, the CO
2
 or O
2
 must be reset. CO
2
 or O
2
 
will have changed when the manifold pressure was 
adjusted. Open the air shutter(s) to reduce the CO
2
 or 
O
2
 to the values achieved previously.
The procedure is complete when all gas valves 
are adjusted to a manifold pressure of 3.0 in. W.C. 
(0.75 kPa) and the CO
2
 is adjusted to 8.0% for Natural 
Gas appliances or 9.2% for LP appliances. When using 
an O
2
 analyzer, the correct O
2
 is 6.8% for both Natural 
Gas and LP appliances.
 Caution
Should any odor of gas be detected, or if the gas 
burner does not appear to be functioning in a 
normal manner, close main shutoff valve, do not 
shut off switch, and contact your heating contractor, 
gas company, or factory representative.
6.5  Shutting Down the Copper Brute II
1.      Switch off the main electrical disconnect switch.
2.      Close all manual gas valves.
3.      If freezing is anticipated, drain the heater and be 
sure to also protect building piping from freezing.
         This step to be performed by a qualified 
service person.
6.6  To Restart the Copper Brute II
If drained, follow Section 6.1 in this manual for 
proper filling and purging.
1.      Switch off the main electrical disconnect switch.
2.      Close all manual gas valves.
3.      WAIT FIVE (5) MINUTES.
4.      Set the aquastat or thermostat to its lowest 
setting.
5.      Open all manual gas valves.
6.      Reset all safety switches (pressure switch, 
manual reset high limit, etc.).
7.      Set the temperature controller to the desired 
temperature setting and switch on electrical 
power.
8.      Burner will go through a prepurge period and 
ignitor warm-up period, followed by ignition.
SECTION 7.
Maintenance
7.1  System Maintenance
1.      Lubricate the system water-circulating pump, if 
required, per the instructions on the pump. 
2.      If a strainer is employed in a pressure reducing 
valve or the piping, clean it every six months.
3.      Inspect the venting system for obstruction or 
leakage at least once a year. Periodically clean 
the screens in the vent terminal and combustion 
air terminal (when used).
4.      Keep the appliance area clear and free from 
combustible materials, gasoline, and other 
flammable vapors and liquids.
5.      If the appliance is not going to be used for 
extended periods in locations where freezing 
normally occurs, it should be isolated from the 
system and completely drained of all water. All 
systems connected to it should also be drained or 
protected from freezing.