Burnham Series 4N Boiler Instruccion De Instalación

Descargar
Página de 24
6
INTRODUCTION
1.  Refer to burner manufacturer’s installation 
manual   provided for proper venting of the 
gas train components that require atmospheric 
pressure to balance a diaphragm. 
2.  All cover plates, enclosures and guards 
must be in place at all times, except during 
maintenance and service.
3.  Insulate all steam and hot water piping, fittings 
and connections and all other hot components 
and equipment from personnel contact..
4.  Assure all pipes, fittings, electrical controls and 
all other associated burner/boiler equipment 
is of proper design and construction for the 
intended use and provides adequate protection 
from electrical shock and harmful physical 
contact to personnel. 
5.  A leak-tight fuel delivery conduit and control 
system must be maintained at all times. 
6.  Products of combustion must be transported 
from the boiler/burner system to the outdoors 
in an approved, leak tight, insulated venting 
system. The boiler room must be positively 
ventilated to prevent a concentration of 
products of combustion and a reduction in the 
amount of oxygen in the air. 
7.  For optimum performance and serviceability  
from this unit adhere to the following  
 
recommendations:
A.  Clean firetubes at least once a year, 
preferably at the end of the heating season 
to remove soot and scale. Inside surfaces of 
the furnace, front and  rear smokeboxes, and 
reversing chamber should also be cleaned 
at the same time.
B. Have the burner and controls checked at 
least  once a year or as necessary.
C. Retain your contractor or a competent 
serviceman to assure that the unit is 
properly adjusted and maintained.
1.  GENERAL INFORMATION
 
The boiler is designed specifically for forced draft 
firing, is available with oil, gas or combination gas/oil 
burners, and operates with a combustion efficiency of 
over 80%.
 
This manual gives the necessary information for 
the proper installation, operation, maintenance and 
service of units. For special installation problems, 
contact Burnham Commercial, P.O. Box 3939 
Lancaster, PA 17604, Phone: 888-791-3790.
SECTION I  —  GENERAL INFORMATION
2.  INSPECT SHIPMENT carefully for any signs of  
 damage.
A.  All Equipment is carefully manufactured,  
inspected and packed. Our responsibility 
ceases upon delivery of boiler to the carrier in 
good condition. 
B.  Any Claims for damage or shortage in 
shipment must be filed immediately against 
the carrier by the consignee. No claims for 
variances from, or shortage in, orders will be 
allowed by the manufacturer unless presented 
within sixty (60) days after receipt of goods.
3.  SETTING THE UNIT
 
Most boilers are equipped with lifting lugs to be 
used in maneuvering the boiler into position. On large 
boilers, where four lifting lugs are supplied, all four lugs 
should be used when lifting the boiler. Scotch boilers 
can also be rolled into position using roller skids under 
the leg supports, pipe rollers may cause damage. 
The unit should be located in the boiler room so as to 
provide ease of venting and adequate clearance for 
maintenance, serviceability and installation of piping.
 
The tube pull space listed in the Burnham 
Commercial product catalog must be provided at 
the front of the boiler.  The coil pull space must be 
maintained at the front of units equipped with tankless 
coils. Floor construction should have adequate load 
bearing characteristics to bear the weight of the boiler 
filled with water. A boiler foundation is recommended 
if the boiler room floor is weak, uneven or if a water 
condition exists. These boilers are not for installation 
on combustible flooring. If desiccant package was 
ordered, be sure to remove from the boiler furnace 
using the rear access, and from the waterside using 
the manhole cover.
4.  CHIMNEY OR vENT
 
On installations where a natural draft stack is 
used, causing high breeching drafts, the boiler locking 
blade damper (on boilers equipped with one) may 
require adjusting, or one may need to be installed at 
the boiler breeching. In multiple boiler installations, 
or in installations where the breeching draft may vary 
considerably, automatic draft controls in combination 
with a motorized damper may be required.
 
When considering the stack and breeching, the 
design should take into account that the boiler/burner 
combination will work best when the pressure at the 
boiler flue outlet is in the range of + or - 1/10 inch WC.