Burnham Series 4N Boiler Instruccion De Instalación

Descargar
Página de 24
8
1.  BOILER PIPING
Attach supply and return piping lines and insert plugs 
and bushings in connections as required. Supply and 
return piping headers are detailed in Figure 2.
It is important to comply with the minimum 
piping requirements in order to ensure maximum 
performance and reliability on steam boilers, 
particular attention should be given to the 
construction of the supply header.
The nominal temperature differential between supply 
and return water recommended for Burnham firetube 
water boilers is 20°F. As a precaution against thermal 
shock, this differential should never exceed 40°F.
When differentials in excess of 30°F are anticipated 
on firebox boilers, the return water should enter the 
boiler  at  the  top  fitting  (normally  the  supply)  and 
the supply water should leave the boiler through 
the  bottom  fitting  (normally  the  return).  This  flow 
pattern directs the return water over the relatively 
cool third pass rather than directly against the rear 
of the furnace. 
The boiler should not be operated for any length 
of time at a temperature setting that allows the 
formation of condensation in the tubes or smokebox. 
This generally dictates a minimum setting of 
approximately 140°F on the low limit on systems 
with a 20°F system differential. On cold start up, 
condensation can be expected until the boiler warms 
up. If formation of condensate persists, the low limit 
should be adjusted upward until condensate no 
longer forms. 
Water boilers and low pressure steam boilers 
must have a set LFH at 120° minimum to avoid 
condensation. High pressure steam should have a 
minimum LFH temperature of 180°F.
 
2.  RECOMMENDED WATER BOILER  
 
 
 
RECIRCULATION LOOP
The following guidelines relating to system water  
 
temperature fluctuation and flow through the boiler  
 
must be observed.
A.   It is important to operate your boiler in such a  
 
manner as to prevent temperature fluctuation of    
more then 40°F at any time. Rapid temperature    
changes within the boiler can create stresses  
 
in the boiler metal. These stresses can cause  
 
damage to the boiler by loosening tubes, or  
 
in more severe instances can crack tube sheet    
ligaments,furnaces, or waterlegs.
B.  If temperature differentials approach 40°F, 
to help prevent temperature fluctuations and 
insure proper circulation through the boiler, a 
recirculation loop as shown in Figure 10 should 
be considered. The recirculation flow should be at 
least 1/2 GPM/BHP at all times when the boiler is 
online for operation.
3.  TANKLESS HEATER
Install an automatic mixing valve at the tankless 
heater outlet to avoid risk of burns or scalding due 
to excessively hot water at the fixtures. Adjust and 
maintain the mixing valve in accordance with the 
manufacturer’s instructions. 
A. If boiler is ordered with tankless heater, connect    
tankless heater piping as shown in Figure 2.
B.  The following guidelines should be followed when  
piping the tankless heaters:
4.  FLOW REGULATION
If flow through the heater is greater than its rating,  
the supply of adequate hot water may not be able to keep up 
with the demand. For this reason a flow regulator matching 
the heater rating should be installed in the cold water line to 
the heater. The flow regulator should preferably be located 
below the inlet so it's not subjected to excess temperatures 
that may occur during “off” periods when it is possible for 
the heat to be conducted back through the supply line. The 
flow regulator also limits the flow of supply water regardless 
of inlet pressure variations in the range of 20 to 120 psi. 
SECTION II  — INSTALLATION INSTRUCTIONS
FIGURE 2
SCHEMATIC TANKLESS HEATER PIPING