FRONT 
OF 
BOILER
SMOKEPIPE -  DO NOT REDUCE BELOW
                           SIZE OF COLLAR ON REAR
 SMOKEBOX
THIMBLE
FIGURE 1
TYPICAL ARRANGEMENT FOR STUB VENT
TS-71-129-B
5.  AIR SUPPLY
 
A sufficient air supply must be maintained at all 
times to the boiler room for proper performance of the 
unit. A permanent opening or duct should be provided so 
that the boiler input will not exceed 4,000 Btuh/in
2
 of free 
area. 
Example: Firing Rate (Gas) = 528 MBH
528,000 BTUH  = 132 In
2
 Free Area
4,000 BTUH/In
2
Follow local building codes if they exceed these minimum requirements.