36
© 2014 Schneider Electric All Rights Reserved
Chapter 4—Front panel display and meter setup
PowerLogic™  PM5300 series user guide
Related topics
Communications setup
After wiring the meter’s serial and Ethernet communications ports, you can configure 
these ports so you can connect to the meter remotely and use device configuration 
software such as ION Setup to configure the meter.
Based on the reference model, the meter is equipped with the following communication 
ports:
Communication ports
Setting up serial communications
The Serial Port setup screen allows you to configure the meter’s RS-485 
communications port so you can use software to access the meter’s data or configure 
the meter remotely.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0000”), then press OK.
3. Press Comm.
4. Move the cursor to point to the parameter you want to modify, then press Edit.
5. Modify the parameter as required, then press OK.
6. Move the cursor to point to the next parameter you want to modify, press Edit
make your changes, then press OK.
Reference Models
Communication
PM5310
RS-485
PM5320
Ethernet
PM5330
RS-485
PM5331
RS-485
PM5340
Ethernet
PM5341
Ethernet
Serial communications setup menu tree
Maint
Reset
Setup
Meter
Comm