PowerLogic™  PM5300 series user guide 
Chapter 4—Front panel display and meter setup
© 2014 Schneider Electric All Rights Reserved
37
7. Press   to exit. Press Yes to save your changes.
Setting up Ethernet communications
The Ethernet Port setup screen allows you to assign the meter a unique IP address so 
you can use software to access the meter’s data or configure the meter remotely 
through the Ethernet port. Before configuring the Ethernet parameters, make sure you 
obtain your meter’s IP address information from your network administrator or IT 
department.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0000”), then press OK.
3. Press Comm.
4. Move the cursor to point to the parameter you want to modify, then press Edit.
5. Modify the parameter as required, then press OK.
6. Move the cursor to point to the next parameter you want to modify, press Edit
make your changes, then press OK.
Communications setup parameters
Parameter
Values
Description
Protocol
Modbus
The communications format used to transmit data. The 
protocol must be the same for all devices in a 
communications loop.
Address
1 to 247
Set the address for this device. The address must be 
unique for each device in a communications loop. For 
Jbus protocol, set the device ID to 255.
Baud Rate
9600, 19200, 38400
Select the speed for data transmission. The baud rate 
must be the same for all devices in a communications 
loop.
Parity
Even, Odd, None
Select None if the parity bit is not used. The parity 
setting must be the same for all devices in a 
communications loop.
Ethernet communications setup menu tree
Maint
Reset
Setup
Meter
Comm