Chapter 4—Front panel display and meter setup
PowerLogic™  PM5300 series user guide
3. Navigate to Meter > Advan.
4. Move the cursor to point to the parameter you want to modify, then press Edit.
5. Modify the parameter as required, then press OK.
6. Move the cursor to point to the next parameter you want to modify, press Edit
make your changes, then press OK.
7. Press Yes to save your changes.
Related topics 
Setting up the alarm / energy pulsing LED
The LED setup screen allows you to configure the alarm / energy pulsing LED for 
alarming or energy pulsing application.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0000”), then press OK.
3. Navigate to I/O > LED.
4. Press Edit.
5. Press   or   to modify the parameter as required, then press OK.
6. Press   to exit. Press Yes to save your changes.
Advanced setup parameters
Parameter
Values
Description
Label
-----
This label identifies the device, e.g., “Power 
Meter”. You cannot use the front panel to edit 
this parameter. Use ION Setup to change the 
device label.
Load Timer Setpt (A)
0 - 99999
Specifies the minimum average current at the 
load before the timer starts. The meter begins 
counting the operating time whenever the 
readings are equal to or above this average 
current threshold.
Pk I dmd for TDD (A)
0 - 99999
Specifies the minimum peak current demand 
at the load for inclusion in total demand 
distortion (TDD) calculations. If the load 
current is below the minimum peak current 
demand threshold, the meter does not use the 
readings to calculate TDD. Set this to “0” 
(zero) if you want the power meter to use the 
metered peak current demand for this 
calculation.
Alarm / energy pulsing LED settings menu tree
LED setup parameter
Parameter
Values
Description
Mode
Off, Alarm, Energy
Off disables the LED.
Alarm sets the LED for alarm notification.
Energy sets the LED for energy pulsing.
Maint
Reset
Setup
Meter
Comm
Alarm
HMI
Clock
LED
Relay
I/O
D Out
S In