Schneider Electric PM5300 Manual De Usuario

Descargar
Página de 120
50
© 2014 Schneider Electric All Rights Reserved
Chapter 6—Input / Output
PowerLogic™  PM5300 series user guide
Related topics
See “Technical Specifications” on page 15 for electrical characteristics and limits for 
the status inputs.
Status input setup
The status input ports (S1 and S2) can be configured using the front panel or 
ION Setup software.
NOTE:
It is recommended you use ION Setup to configure the status inputs, as setup 
parameters that require text entry can only be modified using ION Setup.
Configuring status inputs using ION Setup
You can use ION Setup to configure the status inputs.
1. Start ION Setup.
2. Connect to your meter.
3. Navigate to I/O configuration > I/O Setup.
4. Select a status input to configure and click Edit. The setup screen for that status 
input is displayed.
5. Enter a descriptive name for the status input’s Label.
6. Configure the other setup parameters as required.
7. Click Send to save your changes.
Status input setup parameters available through ION Setup
Parameter
Values
Description
Label
Use this field to change the default label and assign a 
descriptive name to this status input.
Control Mode
Normal, Demand Sync, Input 
Metering
This field displays how the status input functions.
Normal: the status input is not associated with 
another meter function. The meter counts and 
records the number of incoming pulses normally.
Demand Sync: the status input is associated with 
one of the input sync demand functions. The meter 
uses the incoming pulse to synchronize its demand 
period with the external source.
Input Metering: the status input is associated with 
one of the input metering channels. The meter 
counts and records the number of incoming pulses 
and related consumption data associated with the 
pulses.
Debounce
0 to 9999
Debounce is the time delay that compensates for 
mechanical contact bounce. Use this field to set how 
long (in milliseconds) the external signal must remain in 
a certain state to be considered a valid state change.
Associations
This field displays additional information if the status 
input is already associated with another meter function.