Schneider Electric PM5300 Manual De Usuario

Descargar
Página de 120
52
© 2014 Schneider Electric All Rights Reserved
Chapter 6—Input / Output
PowerLogic™  PM5300 series user guide
Digital output applications
Digital outputs are typically used in switching applications, for example, to provide 
on/off control signals for switching capacitor banks, generators, and other external 
devices and equipment. They can also be used in demand synchronization 
applications, where the meter provides pulse signals to the input of another meter to 
control its demand period.
The digital output can also be used in energy pulsing applications, where a receiving 
device determines energy usage by counting the kWh pulses coming from the meter’s 
digital output port.
NOTE:
Be aware that an unexpected change of state of the digital outputs may result 
when the supply power to the meter is interrupted or after a meter firmware upgrade.
Digital output application example
You can connect your meter’s digital outputs to other meters to send a demand sync 
pulse. In the following example, the first meter (Meter 1) controls and sets the demand 
period of the other meters (Meter 2, Meter 3, Meter 4) through the output pulse 
occurring at the end of the first meter’s demand interval.
Related topics
See “Technical Specifications” on page 15 for electrical characteristics and limits for 
the digital outputs.
Digital output setup
The digital output ports (D1 and D2) can be configured using the front panel or 
ION Setup.
NOTE:
It is recommended you use ION Setup to configure the digital outputs, as setup 
parameters that require text entry can only be modified using software.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe electrical 
work practices. See NFPA 70E in the USA or applicable local standards.
• Turn off all power supplying this device before working on it.
• Always use a properly rated voltage sensing device to confirm that all power is off.
• Do not exceed the device’s ratings for maximum limits.
• Do not use this device for critical control or protection applications where human or 
equipment safety relies on the operation of the control circuit.
Failure to follow these instructions will result in death or serious injury.
Digital output wiring example
S1
S2
D1 D2
-/C
+
(60) (62) (40) (42) (57) (56)
S1 -/C
S1 -/C
S1 -/C
< 20mA
  
< 40Vdc
< 40Vdc
< 20mA
  
Meter 2
Meter 3
Meter 4
Meter 1