Schneider Electric PM5300 Manual De Usuario

Descargar
Página de 120
54
© 2014 Schneider Electric All Rights Reserved
Chapter 6—Input / Output
PowerLogic™  PM5300 series user guide
Configuring digital outputs using the front panel
You can use the front panel to configure the digital outputs.
1. Navigate to Maint > Setup.
2. Enter the setup password (default is “0000”), then press OK.
3. Navigate to I/O > D Out.
Select Alarms
1.
Over Current, Ph; 
2.
Under Current, Ph; 
3.
Over Current, N;
4.
Over Current Gnd;
5.
Over Voltage, L-L; 
6.
Under Voltage, L-L; 
7.
Over Voltage, L-N; 
8.
Under Voltage L-N; 
9.
Over kW; 
10. Over kVAR; 
11. Over kVA; 
12. Lead PF, True; 
13. Lag PF, True; 
14. Lead PF, Disp; 
15. Lag PF, Disp; 
16. Over kW Dmd, Pres; 
17. Over kW Dmd, Last; 
18. Over kW Dmd, Pred; 
19. Over kVAR Dmd,Pres;
20. Over kVAR Dmd,Last; 
21. Over kVAR Dmd,Pred; 
22. Over kVA Dmd, Pres; 
23. Over kVA Dmd, Last; 
24. Over kVA Dmd, Pred; 
25. Over Frequency; 
26. Under Frequency; 
27. Over Voltage Unbal;
28. Over Voltage THD; 
29. Phase Loss; 
30. Meter Powerup; 
31. Meter Reset;
32. Meter Diagnostic; 
33. Phase Reversal;
34. Digital Alarm S1;
35. Digital Alarm S2;
Applies when Control Mode is set to Alarm. Select 
one or more alarms to monitor.
Associations
This field displays additional information if the digital 
output is already associated with another meter 
function.
Digital output setup menu tree
Digital output setup parameters available through ION Setup (continued)
Parameter
Values
Description
Maint
Reset
Setup
Meter
Comm
Alarm
HMI
Clock
LED
Relay
I/O
S In
D Out