PowerLogic™  PM5300 series user guide 
Chapter 6—Input / Output
© 2014 Schneider Electric All Rights Reserved
53
Configuring digital outputs using ION Setup
You can use ION Setup to configure the digital outputs (D1 and D2).
1. Start ION Setup.
2. Connect to your meter
3. Navigate to I/O configuration > I/O Setup.
4. Select a digital output to configure and click Edit. The setup screen for that digital 
output is displayed.
5. Enter a descriptive name for the digital output’s Label.
6. Configure the other setup parameters as required.
7. Click Send to save your changes.
Digital output setup parameters available through ION Setup
Parameter
Values
Description
Label
Use this field to change the default label and assign a 
descriptive name to this digital output.
Control Mode
External, Demand Sync, 
Alarm
This field displays how the digital output functions.
External: the digital output is controlled remotely 
either through software or by a PLC using 
commands sent through communications.
Demand Sync: the digital output is associated 
with one of the demand systems. The meter 
sends a pulse to the digital output port at the end 
of every demand interval.
Alarm: the digital output is associated with the 
alarm system. The meter sends a pulse to the 
digital output port when the alarm is triggered.
Behavior Mode
Normal, Timed, Coil Hold
Normal: this mode applies when control mode is 
set to External or Alarm. The digital output 
remains in the ON state until an OFF command is 
sent by the computer or PLC.
Timed: the digital output remains ON for the 
period defined by the On Time setup register.
Coil Hold: this mode applies when control mode 
is set to External or Alarm. For a unary alarm that 
is associated with a digital output, you must set 
Behavior Mode to Coil Hold. The output turns on 
when the “energize” command is received and 
turns off when the “coil hold release” command is 
received. In the event of a control power loss, the 
output remembers and returns to the state it was 
in when control power was lost.
On Time (s)
0 to 9999
This setting defines the pulse width (ON time) in 
seconds.
Select Dmd System
Power, Current
Applies when Control Mode is set to Demand Sync. 
Select the demand system to monitor.