Schneider Electric 750VA Manual De Usuario

Descargar
Página de 20
7
Smart-UPS X-Series Operation
Controllable Outlet Groups
Overview
The rear panel of the UPS has multiple outlets, some are grouped into Controllable Outlet Groups, all 
others are the UPS outlets. All of these groups can be configured to turn off, turn on, shut down, and 
reboot connected equipment, independently of each other. 
The Controllable Outlet Groups and the UPS outlets can be configured to react to power events in 
specific ways:
•  Turn off: Disconnect from power immediately and restart only with a manual command
•  Turn on: Connect to power immediately
•  Shutdown: Disconnect power in sequence, and automatically reapply power in sequence when 
utility power becomes available
•  Reboot: Shut down and restart
In addition, the Controllable Outlet Groups and the UPS outlets can also:
•  Turn on or off in a specified sequence
•  Shut down when various conditions occur
Note: If the Controllable Outlet Groups are not configured, all of the outlets on the unit will 
still provide battery back-up power.
Nominal Output 
Voltage
230 V: 230 VAC
230 V: 220, 230, 240 
VAC
Set the nominal output voltage of the UPS on 
battery. This is available on 230V models 
only.
Transfer 
Sensitivity
High
High, Low, Medium
Specify how sensitive the UPS will be 
towards voltage changes.
Low Battery 
Warning
90 sec
0-300 sec
The UPS will emit an audible alarm when the 
remaining runtime has reached this level.
Date of Last 
Battery 
Replacement
Date set at factory Reset this date when the battery module is replaced.
Audible Alarm On
On/Off
The UPS will mute all audible alarms if this is 
set to Off or when the display buttons are 
pressed.
Battery Self-
Test Interval 
Setting
On start-up and 
every 14 days since 
the last test
• Never
• Start-up only
• Frequency of test
The interval at which the UPS will execute a 
self-test.
Reset to Factory 
Default
No
Yes/No
Restore the UPS factory default settings.
Function
Factory Default Options
Description