Smart-UPS X-Series Operation
6
Configuration
UPS Settings
Start-up Settings
Configure these settings at initial start-up, using the display interface or APC PowerChute
®
 software.
Note: During start-up, use the display interface to configure these settings. If nothing is 
selected, the until will use the default settings.
General Settings
Configure these settings at any time, using the display interface or APC PowerChute software.
Function
Factory Default Options
Description
Language
English
• English
• French*
• German*
• Spanish*
• Italian*
The language for the display interface.
*Language options will vary by model.
Local power 
quality
Good
• Good
• Fair
• Poor
Select the quality of input utility power.
• If Good is selected, the unit will go on battery 
power more often to provide the cleanest power 
supply to the connected equipment.
• If Poor is selected, the UPS will tolerate more 
fluctuations in power and will go on battery power 
less often. 
If unsure of the local power quality, select Good.
Menu Type
Standard
Standard or 
Advanced
The advanced menus include all parameters. The 
Standard menus display a limited set of menus and 
options.
Display 
Mode
Always On
Always On or 
Power Saving
The display may be always on or may be set to 
automatically turn on only when using the 
configuration buttons or if an event occurs.
Function
Factory Default Options
Description
High transfer 
point
120 V: 140 VAC
120 V: 140-150 VAC To avoid unnecessary battery usage, set the 
transfer point higher if the utility voltage is 
chronically high and the connected equipment 
is known to work under this condition. This 
setting may also be adjusted using the power 
quality setting.
230 V: 280 VAC
230 V: 280-300 VAC
Low Transfer 
Point
120 V: 75 VAC
120 V: 75-85 VAC
Set the transfer point lower if the utility 
voltage is chronically low and the connected 
equipment can tolerate this condition.This 
setting may also be adjusted using the power 
quality setting.
230 V: 170 VAC