GE LP 33 Manual De Usuario

Descargar
Página de 57
Modifications reserved 
Page 19/57 
OPM_LPS_3UO_30K_40K_0US_V010.doc 
Operating Manual LP 33 Series 30 & 40 kVA 
5 SYSTEM 
HANDLING 
 
 
5.1 CONTROL 
PANEL 
 
 
Fig. 5.1-1   Control panel 
 
LCD screen 
Shows the UPS system data, events messages and UPS setting. 
The data is displayed on 4 rows, 20 characters each, allowing the operator to select 
between 7 languages: English, German, French, Spanish, Italian, Finnish or Polish
If there is no keypad activity during 1 minute the LCD screen will return to default 
screen. 
 
 
Metering 
Shows electric parameters, operating statistics and some information screens (see 
Section 6.1). 
 
 
Alarm 
Shows in chronological order, all the events occurred (alarms, messages, 
commands, handling, etc.) and resets general alarm / buzzer (see Section 6.2). 
 
 
Menu 
Allows the user to adapt certain features of the UPS to his needs, to reset the 
command total off, to test the LEDs panel, and to command the inverter ON/OFF (see 
Section 6.3). 
 
 
Scroll to following screen. 
Entering in PARAMETER MENU/USER, allows to select the horizontal editable 
position. 
 
 
Entering in Alarm and Metering, scroll to previous screen. 
Entering in menu allows to select the row including the needed command. 
 
 
Enter 
Confirms the selected command. 
Entering in PARAMETER MENU/USER allows the user to change the parameters. 
 
 
LED Alarm 
(red)
 
It warns about the imminent inverter stop and the consequent load shutdown as 
result of: 
•  The  battery is fully discharged and the load cannot be transferred on mains 
(default parameter = 3 min.). 
•  Overtemperature (default = 3 min.) or overload condition (125%-10 min, 150%-1 
min.) and the load cannot be transferred on mains
 
 
LED Warning 
(yellow)
 
When blinking, it means the UPS is in alert condition with the buzzer sounding. 
The yellow LED will remain lit after pressing the key Alarm
It remains lit also when the output switch Q1 is open or battery disconnected. 
 
 
LED Operation 
(green) 
When lit, it means the UPS is correctly operating and the load is powered by the 
inverter. When blinking, it means SERVICE REQUIRED