Operating Manual LP 33 Series 30 & 40 kVA 
5.2  COMMAND PUSH BUTTONS AND SWITCHES 
 
 
total off 
Press simultaneously the keys Alarm and - on the 
panel. 
This will cause the opening of all contactors  (K4,  K6 
and  K7), shutdown of booster,  Inverter,  battery-
charger
 and SSM. 
 
 
In a parallel system pressing total off 
on one unit all the units will shut 
down. 
 
 
NOTE ! 
Using the command total off, the load will 
be immediately powered down. 
 
To restart the unit, command total off must be 
restored entering the screen
 
 
Fig. 6.2-1   Command total off 
 
MENU/RESET TOTAL OFF
 
LAMP TEST 
RESET TOTAL OFF 
* 
 
 
 
 
 
 
 
 
 
Q1 - UPS output switch 
Q2 - Manual bypass switch 
 
 
NOTE ! 
Do not switch ON Q1 and Q2 with 
Inverter ON
 
 
Fig. 6.2-2   Q1 & Q2 switches 
 
 
 
 
 
 
NOTE ! 
Mains failure of long duration or low Battery voltage will cause the automatic 
shutdown of the UPS, thus preventing damage to the Battery.