GE LP 33 Manual De Usuario

Descargar
Página de 57
Modifications reserved 
Page 37/57 
OPM_LPS_3UO_30K_40K_0US_V010.doc 
Operating Manual LP 33 Series 30 & 40 kVA 
7.1.2 
UPS shutdown with load transfer on manual bypass (Q2) 
 
The purpose of this procedure is to supply the load directly by mains through manual bypass Q2
 
This procedure is normally performed when the UPS must be completely switched OFF for maintenance 
or service purpose, performed by an authorized Service Center
 
 
 
NOTE ! 
This procedure must not be performed if the UPS is used as frequency converter
 
 
 
 
1.  Switch OFF the inverter by entering the screen
MENU/COMMAND MENU/INVERTER OFF 
Attention
:  to switch OFF permanently the inverter the key 
Enter must be pressed 2 times
 
COMMAND MENU
 
INVERTER ON 
INVERTER OFF *
 
 
 
The output will be supplied by the mains through the automatic 
bypass.
 
 
LP 33          40kVA 
APPLICAT. ON UTILITY 
= 70% 
 
 
2.  Switch ON the maintenance bypass Q2 (Pos. I). 
 
LP 33          40kVA 
APPL. ON MANUAL DEV. 
= 70% 
 
 
3.  Switch OFF the output switch Q1 (Pos. 0)
 
4.  Perform the command total off. 
 
5.  Remove the battery fuses F5, F6, F7 and eventual external fuses in case of external battery
 
 
 
 
Continue 
►