GE LP 33 Manual De Usuario

Descargar
Página de 57
Modifications reserved 
Page 53/57 
OPM_LPS_3UO_30K_40K_0US_V010.doc 
Operating Manual LP 33 Series 30 & 40 kVA 
8 OPTIONS 
 
 
8.1  OPTIONS GENERAL VIEW 
 
LPS33U_030-040_RPA system_GE_01
LP 33 Series
1
RPA
Board
LP 33 Series
2
RPA
Board
LP 33 Series
3
RPA
Board
LP 33 Series
4
RPA
Board
F2
F1
F3
F4
UTILITY INPUT
LOAD
 
RPA kit 
Redundant Parallel Architecture
 
Allows to extend the unit to a parallel system with 2, 3, or 4 units 
connected on the same bus, which ensure the highest reliability rate 
and increase the power availability without prior investments. 
 
 
LPS
33U
_OP
T _C
abin
et ba
ttery
_01
 
Additional battery charge 
For battery with extended backup time (max. 15A). 
Dimensions (WxDxH): 16.93” x 28.55” x 70.95” / 430 x 725 x 1802 mm 
 
 
S
G
T
400
0_
cu
st
om
er
 int
e
rf
ac
e_
02
123
456789
10
11
16
15
14
13
12
22
21
20
19
18
17
2
1
 
Customer Interface 
The Customer Interface allows the client the exchange of information 
(monitoring and control) with the following interfaces: 
•  Serial port RS232
•  6 programmable output channels. 
•  2 programmable input channels, of witch one for GEN-ON
• 
EPO (Emergency Power Off).
 
 
 
 
Advanced SNMP Card 
Simple Network Management Protocol 
The  Advanced SNMP Card is an interface to the Ethernet 
Network
, and provides UPS information via the standard SNMP 
Protocol (UPS-MIB (RFC-1628); GE Single MIB; GE Parallel MIB). 
The UPS can therefore be managed by a Network Management 
System (NMS)
 or by our applications (for instance JUMP), which 
uses this information to determine the state of the UPS in order 
to guarantee safe and orderly shutdown of the server, when 
needed. 
 
 
 
Connectivity Software 
JUMP Software Suite / IRIS Service, etc
Software application for the control and monitoring of the UPS.