7.2.8  Restore to normal operation after “EPO – Emergency Power Off” 
 
 
NOTE ! 
Make sure the all units of the parallel system to be status of the activation of EPO, i. e. 
Q1
 closed, Q2 open and the battery fuses F5, F6, F7 (and eventual external fuses in case 
of external battery) connected. 
 
 
View of the panel after pressing the button “EPO”
• 
All Contactors are open. 
• 
Booster, inverter and Static-Switch shutdown. 
 
LP 33          40kVA  P1 
APPLICAT. SUPPLY OFF 
= 0% 
 
 
 
 
1.  Reset the button “EPO”. 
Press Alarm, to reset alarm and buzzer
 
01.01.2005 12:15:45 
NR=255 Status=A588 
4563: 
EMERGENCY OFF 
ACTIVATED 
 
2.  Reset all UPS by entering the screen
MENU/COMMAND MENU/INVERTER OFF 
The load is supplied by the mains through the automatic 
bypass
 
COMMAND MENU 
INVERTER ON * 
INVERTER OFF 
 
The booster starts automatically.
 
 
The LCD screen must display on all Units the status: 
APPLICATION ON BYPASS
 
 
LP 33          40kVA  P1 
APPLICATION ON BYPASS 
= 70% 
 
 
3.  Switch ON the inverter on first unit by entering the screen
MENU/COMMAND MENU/INVERTER ON 
In case of sufficient output power, the output will transfer to 
Inverter 
 
COMMAND MENU 
INVERTER ON * 
INVERTER OFF 
 
 
4.  Switch ON the inverter on the other units by entering the 
screen: MENU/COMMAND MENU/INVERTER ON 
(Do not start the next inverter until the sequence of the previous
one ends – about 10 seconds).
 
 
MENU COMANDI 
INVERTER ON * 
INVERTER OFF 
 
 
LP 33          40kVA  P1 
APPLICATION ON UPS 
= 70% 
 
As soon as the output power of the inverters is sufficient to 
supply the load, the output of the units with running inverter 
will transfer to inverter
The LCD screen must display on all Units the status: 
APPLICATION ON UPS
 
 
 
 
END OF PROCEDURE