Mounting
Mount the TAC DuraDrive Actuator directly on the damper shaft in locations that clear the 
maximum dimensions of the actuator case and allow the actuator to be mounted flush to the 
surface of the terminal box and perpendicular to the damper shaft.
Note: Some terminal boxes have sheet metal screw heads or other protrusions near the 
damper shaft. In these cases, a spacer or shim may be added under the mounting tab of 
the actuator to make the actuator perpendicular to the shaft.
Caution: To remain in NEMA 2 compliance the MS40-715X and MS40-707X series 
actuators should be mounted with conduit end down.
Damper Actuator Sizing
Correct sizing of the actuator is necessary for proper control of dampers. The area of 
damper that can be controlled by a given actuator is dependent upon the quality of the 
damper, the pressure drop across the damper in the closed position, and the velocity of the 
air flow through the damper. To obtain actual damper torque requirements, contact the 
damper manufacturer.
Damper Shaft Sizing 
Use the “Long Damper Shaft” mounting instructions if the damper shaft is at least 4-5/8" 
(117 mm) long.
Use the “Short Damper Shaft” mounting instructions if the damper shaft is shorter than 4-5/8" 
or the area around the damper shaft is too narrow to allow standard mounting, as described 
in the “Long Damper Shaft” mounting section. See Figure-9 for minimum shaft length.
Caution: The MS40-717X actuator is not designed to be used on aluminum damper 
shafts, solid steel shafts smaller than 1/2" diameter round or 1/2" square, or hollow steel 
shafts smaller than 3/4" round. The actuator can produce up to 545 in-lbs (61.8. N-m) 
maximum stall torque, which could result in the actuator snapping off an aluminum damper 
shaft or an improperly sized steel damper shaft. Refer to Table-2 for nominal damper shaft 
sizes.
Table-2 Steel Damper Shaft Specifications.
Figure-9 Long Damper Shaft Dimensions.
Min. 4-5/8" (117 mm)
Damper Shaft Shape
Damper Shaft Type
O.D. (Nominal)
a
I.D. (Maximum)
Round
Solid bar
1/2" to 1"
0
Hollow tubing
3/4"
0.375
13/16"
0.683
27/32"
0.626
7/8"
0.805
15/16"
0.808
1"
0.930
Square
Solid bar
1/2" to 5/8"
0
a
Damper shaft sizes over 1/2" (13 mm) O.D. require AM-753 universal mounting clamps.