Reference Manual 
00809-0100-4027, Rev AA
December 2005
4-3
Rosemount 4500
Figure 4-1 also identifies the approximate transmitter location for each 
calibration task. Data flows from left to right, and a parameter change affects 
all values to the right of the changed parameter.
Not all calibration procedures should be performed for each 4500 transmitter. 
Some procedures are appropriate for bench calibration, but should not be 
performed during field calibration. Table 4-1 identifies the recommended 
calibration procedures for bench or field calibration.
Figure 4-1. Transmitter Data 
Flow with Calibration Options
 
Transmitter Ranged 0 to 100 inH
2
O (0 to 0,25 bar)
NOTE
Value on PV line should equal the input pressure.
Value on AO line should equal the output device reading.
CALIBRATION
A/D
MICRO
D/A
20.00 mA
100 in. H
2
0
4500:LT-8793
Online
1
Device setup
2
PV
100.00 in.H
2
0
3
AO
20.00 mA
4
LRV
0.00 in.H
2
0
5
URV
100.00 in.H
2
0
SAVE