Emerson Process Management 2400S Manuel D’Utilisation
Configuration and Use Manual
27
Required Transmitter Configuration
Req
u
ir
ed
Con
Con
fig
uration
Opt
ion
al Co
al Co
nfi
g
g
u
ratio
n
Using the
T
ransmitter
Usin
g a PR
OF
IB
US
IB
US
Ho
st
st
When configuring the flow calibration factor:
•
Using ProLink II, enter the concatenated 10-character string exactly as shown, including the
decimal points. For example, using the Flow Cal value from Figure 6-1, enter
decimal points. For example, using the Flow Cal value from Figure 6-1, enter
19.0005.13
.
•
Using other methods, you may be required to enter the concatenated value, or you may be
required to enter the two factors separately, i.e., enter a 6-character string and a 4-character
string. Include the decimal point in both strings. For example, using the Flow Cal value from
Figure 6-1:
required to enter the two factors separately, i.e., enter a 6-character string and a 4-character
string. Include the decimal point in both strings. For example, using the Flow Cal value from
Figure 6-1:
-
Enter
19.000
for the flow calibration factor.
-
Enter
5.13
for the temperature coefficient for flow.
6.2.3
How to characterize
To characterize the flowmeter:
1. See the menu flowcharts in Figure 6-2.
2. Ensure that the correct sensor type is configured.
3. Set required parameters, as listed in Table 6-1.