Cisco Metro 1500 Series Hardware Installation Guide
78-10588-03
Chapter 3
Installing the Chassis
Connecting Power
Step 5
Turn the power on using the corresponding power switch of the PDU.
The chassis powers up as soon as the corresponding power switch of the PDU is
turned on. If the DC power cables are not connected to the PDU, the plug socket
combinations on the rear end of the unit serve as switches.
Power Consumption and Power Supply Fuses
The system power consumption is less than 150 W.
Use the following fuses:
Caution
Always replace blown fuses with fuses of the same type and size.
Caution
Do not use damaged terminal blocks. Immediately replace damaged
or defective terminal blocks.
Note
The 115/230V version automatically detects the input voltage. No
further adjustment is necessary.
The Cisco Metro 1500 series system supports the following power sources:
Power Type
Fuse Type
No. of Fuses
AC version
2.5A at 250V, slow blow, 5 x 20 mm
2
DC version
6.3A at 250V, slow blow, 5 x 20 mm
2
AC
110 to 240V, 50 or 60 Hz
DC
-48 to -60V