FirePLAce inStALLAtiOn
Continued
CHECKING GAS CONNECTIONS
 WARNING: Test all gas piping 
and  connections,  internal  and 
external to unit, for leaks after 
installing or servicing. Correct 
all leaks at once.
  WARNING:  Never  use  an 
open flame to check for a leak. 
Apply noncorrosive leak detec-
tion fluid to all joints. Bubbles 
forming show a leak. Correct all 
leaks at once.
pRESSURE TESTING GAS SUppLY 
pIpING SYSTEM 
Test Pressures In Excess Of 1/2 PSIG 
(3.5 kPa)
1.  Disconnect  fireplace  and  its  individual 
equipment shutoff valve from gas supply 
piping system. Pressures in excess of 1/2 
psig (3.5 kPa) will damage fireplace gas 
regulator.
2.  Cap off open end of gas pipe where equip-
ment shutoff valve was connected.
3.  Pressurize supply piping system by either 
opening  propane/LP  supply  tank  valve 
for propane/LP gas fireplace or opening 
main gas valve located on or near gas 
meter for natural gas fireplace or using 
compressed air.
4.  Check all joints of gas supply piping sys-
tem. Apply  noncorrosive  leak  detection 
fluid to all joints. Bubbles forming show a 
leak. Correct all leaks at once.
5.  Reconnect  fireplace  and  equipment 
shutoff valve to gas supply. Check recon-
nected fittings for leaks. 
Test Pressures Equal To or Less Than 
1/2 PSIG (3.5 kPa)
1.  Close equipment shutoff valve (see Fig-
ure 21).
2.  Pressurize supply piping system by either 
opening  propane/LP  supply  tank  valve 
for propane/LP gas fireplace or opening 
main gas valve located on or near gas 
meter for natural gas fireplace or using 
compressed air.
Figure 21 - Equipment Shutoff Valve
Open
Closed
Equipment 
Shutoff Valve
3.  Check all joints from propane/LP supply 
tank or gas meter to equipment shutoff 
valve (see Figure 22 or Figure 23). Apply 
noncorrosive  leak  detection  fluid  to  all 
joints. Bubbles forming show a leak.
4.  Correct all leaks at once.
Figure 22 - Checking Gas Joints for 
Propane/LP Gas Fireplace
Propane/LP 
Supply Tank
Gas Valve
Equipment 
Shutoff Valve
pRESSURE TESTING FIREpLACE GAS 
CONNECTIONS
1.  Open equipment shutoff valve (see Fig-
ure 21).
2.  Open propane/LP supply tank valve for 
propane/LP fireplace or main gas valve 
located on or near gas meter for natural 
gas fireplace.
Gas Meter
Gas Valve
Equipment 
Shutoff Valve
Figure 23 - Checking Gas Joints for 
Natural Gas Fireplace