Friedrich RC/RH 10 Manuel D’Utilisation

Page de 26
13
www.retroaire.com
The Right Fit For Comfort
*Refer to the charts on page 23 for electrical and optional 
electric heat specifications.
1. Take unit out of packaging. 
2. Slide unit into wall-sleeve. The supply duct on the cool-
ing chassis should line up with the supply vent on the 
room cabinet.
3. Slide unit out of wall-sleeve
IMPORTANT: The correct condenser air baffles must 
be installed or performances may be impaired and/or 
the warranty will be voided. 
4. Baffle Installation - Remove baffles from kit bag sup-
plied with unit. Install left and right side baffles on the 
condenser coil in existing holes: 
6. Once confident that all seals are the correct size and in 
the proper location and the correct baffles are attached 
to the condenser coil and in the proper orientation, slide 
unit into final position and tighten any tie down bolts or 
screws as necessary.
Hydronic Only: Remove the 2-position connector as-
sembly from kit bag supplied with unit (this will have 2 
yellow wires attached). Connect this 2-position connector 
to the 2-position connection located on the bottom of the 
control box panel. 
To Connect Aquastat: 
A.  Remove  the  black  jumper  wire  located  on  the 
bottom panel of the control box (this is also ter-
minated with a 2-position connector).
B. Cut the jumper wire in the middle and splice the 
aquastat to the jumper. 
C. Place the connecter back into  original location. 
Refer to wire diagram on the unit for details.
7. Connect line cord. 
8. See Final Inspection and Startup on page 20.
IMPORTANT: The RC/RH35 is equipped with a bracket 
that allows the unit to be adjusted up and down in the chas-
sis of unleveled wall sleeves. Adjust leveler leg (Shown 
below Figure B6) to desired height and tighten down using 
bolts supplied on bracket.
RC/RH35 REPLACEMENT PTAC
INSTALLATION INSTRUCTIONS
• 1 Installation Manual
• 1 Lt. & Rt. Baffles
HYDRONIC
 ONLY
• 1ea. 2-Position Connector & Pin Mate
• 14AWG Black Wire
• Screws 
• 1” x 1” Open Cell Foam Tape
RC/RH35  INSTALLATION KIT
RC/RH35 PERFORMANCE DATA*
MODEL COOLING 
Btuh
EER HEAT PUMP 
Btuh
COP FRESH AIR 
CFM
9
9,500
10
8,500
2.8
40/35
12
11,900
10
11,400
2.9
40/35
15
14,700
9.2
13,800
2.8
40/35
18
16,900
9.1
N/A
N/A
40/35
Figure B6
Figure A6
1” X 1” Supply Air 
Duct Foam Tape
Baffles-Directed Inward 
Toward Coil
��������
�������
���
���������������
��������������
•  Baffles  must  come  in 
contact  with  the  out-
door louver.  
• Make sure baffles are 
directed inward toward 
the center of coil. 
•  Secure  baffles  tightly 
to  the  condenser  coil 
using  the  screws  pro-
vided. (Figure A6)
5.  Apply 1” x  1” open cell foam strips around supply air 
duct to ensure that all the conditioned air is delivered 
into the room. Failure to do so results in recirculation of 
the conditioned air around the wall sleeve and through 
the  unit  causing  the  unit  to  short  cycle,  thus  raising 
operating costs through improper heating and cooling 
(Figure A6).