Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
Appendix C: Wiring Requirements
Connecting external system accessories to the AUDIO•COMMAND•CENTER•25/50 Series main 
circuits must be carefully considered to ensure proper operation.  It is important to use the correct 
type of wire, wire gauge and wire run length per each circuit.  Refer to the following table to spec-
ify wire requirements and limitations.
 
NOTE: If an SLC loop is to be run in conduit with AUDIO•COMMAND•CENTER•25/50 Series 
Notification Appliance Circuits, the risk of encountering problems can be greatly reduced by using 
twisted, shielded cable on the SLC and NACs.
CIRCUIT CONNECTIONS
WIRE REQUIREMENTS
Circuit Type
Circuit Function
Wire Type & 
Limitations
Recommended Maximum Distance 
(Feet)
Wire Gauge
AC Power 
TB3 (nonpower-limited)
Primary Power Input to 
ACC-25/50 Series, 
AC Voltage
See Note
1
Power Supplied must be: 
120 VAC, 60 Hz, 1.5 amps (see Note
)
Terminals Support
12-18 AWG
(see Note
)
Audio Output 
ACC-AAM25 Module 
TB1 and
ACC-ZSM Module
(power-limited)
Notification Appliance Circuit
See Note
2
Untwisted, 
unshielded or 
twisted, shielded
See Note
3
12 - 18 AWG
ACC-ZPMK Module
ACS (EIA-485 Circuit
4,000 feet
12 - 18 AWG
ACC-FFT TB1
Telephone Loop
See Note
2
Untwisted
unshielded or
twisted, shielded
54
 maximum impedance
12 - 18 AWG
ACC-FFT TB2
Contact Closure
Input Trigger
Untwisted
unshielded
54
 maximum impedance
12 - 18 AWG
ACC-FFT TB3
Remote Microphone
Connection
4
See Note
4
See Note
4
See Note
4
ACC-EPM Module
External Page Connection
12 - 18 AWG
CMD1 and CMD2 Main 
Board TB2 and TB5
Triggers ACC-25/50 Series
See Note
Untwisted, 
unshielded or 
twisted, shielded
Depends on Output (trigger) Circuit
9 - 32 VDC, 1.6 mA for polarity reversal 
relay must be rated at 0.5 amp, 24 
VDC
12 - 18 AWG
CMD3, CMD4 and 
CMD5 Main Board TB8, 
TB9 and TB10
Triggers ACC-25/50 Series
See Note
Untwisted, 
unshielded or 
twisted, shielded
Depends on Output (trigger) 
Circuit from contact device
12 - 18 AWG
Main Board TB6 Master 
Command Bus Reverse 
Polarity (power-limited)
Output Trigger for Multiple 
ACC-25/50 Series 
configurations
Untwisted, 
unshielded
200 ohms maximum
12 - 18 AWG
Trouble Relay Main 
Board TB1 
Trouble Output
Maximum 
Current 2 amps
Depends on Input Circuit
12 - 18 AWG
AC Loss Relay
Main Board TB7 
AC Loss Output
Maximum 
Current 2 amps
Depends on Input Circuit
12 - 18 AWG
Table C.1  AUDIO•COMMAND•CENTER•25/50 Series Wiring Requirements
1 Refer to NEC Standards.
2 Twisted, shielded wire is recommended for maximum protection against EMI and AFI emissions and susceptibility.
3 Must also meet NFPA 72 Standards for minimum and maximum sound levels.
4 Refer to Remote Microphone Document #51247.