Honeywell 25/50ZS Manuel D’Utilisation

Page de 144
Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
87
ACC-25/50ZS & ACC-25/50ZST Zone Splitting Applications
Application Examples
5.5  ACC-25/50ZS & ACC-25/50ZST Zone Splitting 
Applications
5.5.1  25 Watt Zone Splitting - Eight Speaker Circuits, Style Y 
(Class B)
This application of the ACC-25/50ZS & ACC-25/50ZST configures the Zone Splitter Module 
(ACC-ZSM) to divide 25 watts of audio from one Audio Amplifier (ACC-AAM25) into eight 
speaker circuits.  The FACP uses the ACS link connected to the Zone Page Module (ACC-ZPMK) 
for automatic activation of the speaker zones and for alarm activation.
Configuration switches are set as follows:
ACC-ZSM SW1 set to AAM1 and SW2 to Class B to split one ACC-AAM25 into 8 Style Y 
(Class B) zones
ACC-ZPMK DIP switch S1 set for communication with:
MS-9200UDLS or MS-9200UD with software version 2.x (1=ON, 2=OFF, 3=ON)
MS-9600 with software version 2.x or higher (1=ON, 2=OFF, 3=OFF)
ACC-25/50ZS main circuit board DIP switch S3 set for single zone mode, All-Call and two 
messages (1=ON, 2=OFF, 3=OFF)
The MS-9600, MS-9200UDLS, or MS-9200UD FACP can automatically activate the Fire Evacua-
tion or All Clear Message and any combination of the 8 speaker zones.  Manually deactivating 
speaker circuit is accomplished by pressing the activated zone push-button on the ACC-ZPMK 
keypad.  Manual activation can be performed by pressing either of the Message push-button(s) and 
then selecting the zone push-button on the ACC-ZPMK keypad.  All-Call Paging is possible by 
first pressing the All-Call push-button on the main panel keypad and then keying the microphone to 
make an announcement.