Honeywell 25/50ZS Manuel D’Utilisation

Page de 144
Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
89
ACC-25/50ZS & ACC-25/50ZST Zone Splitting Applications
Application Examples
5.5.2  25 Watt Zone Splitting - Four Speaker Circuits, Style Z 
(Class A)
25 watts total power with automatic control via ACS link from the FACP (see Table 2.7 on page 37, 
Table 2.8 on page 40, and “ACC-ZSM Zone Splitter Module (ACC-25/50ZS & ACC-25/50ZST)” 
on page 41
 for switch settings).
This application of the ACC-25/50ZS/T configures the Zone Splitter Module (ACC-ZSM) to 
divide 25 watts of audio from one Audio Amplifier (ACC-AAM25) into four speaker circuits.  The 
FACP uses the ACS link connected to the Zone Page Module (ACC-ZPMK) for automatic activa-
tion of the speaker zones and for alarm activation.
Configuration switches are set as follows:
ACC-ZSM SW1 set to AAM1 and SW2 to Class A to split one ACC-AAM25 into 4 Style Z 
(Class A) zones
ACC-ZPMK DIP switch S1 set for communication with:
MS-9200UDLS and MS-9200UD with software version 2.x (1=ON, 2=OFF, 3=ON)
MS-9600 with software version 2.x or higher (1=ON, 2=OFF, 3=OFF)
ACC-25/50ZS/T main circuit board DIP switch S3 set for single zone mode, All-Call and two 
messages (1=ON, 2=OFF, 3=OFF)
The MS-9600, MS-9200UDLS, or MS-9200UD FACP can automatically activate the Fire Evacua-
tion or All Clear Message and any combination of the 4 speaker zones.  Manually deactivating a 
speaker circuit is accomplished by pressing the activated zone push-button on the ACC-ZPMK 
keypad.  Manual activation can be performed by pressing either of the Message push-button(s) and 
then selecting the zone push-button on the ACC-ZPMK keypad.  All-Call Paging is possible by 
first pressing the All-Call push-button on the main panel keypad and then keying the microphone to 
make an announcement.