Honeywell 25/50ZS Manuel D’Utilisation

Page de 144
96
Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
Application Examples
Audio Command Center 24 Zone System
5.8  Audio Command Center 24 Zone System
In this application, the Fire Protection System consists of one ACC-25/50ZS panel with two ACC-
25/50DAZS panels, 24 zones and an FACP.  Automatic control by the FACP is provided through 
the ANN-BUS or ACS link to the ACC-25/50ZS.  Manual control is possible via the keypad in the 
ACC-25/50ZS.  Control of Audio Zones 9 - 24 is sent through the ACC Control Serial Link to the 
ACC-25/50DAZS Distributed Audio Panels.  Alarm and Paging audio from the ACC-25/50ZS is 
delivered to Audio Zones 9 - 24 (ACC-25/50DAZS panels) by way of the Audio Riser.