Honeywell 25/50ZS Manuel D’Utilisation

Page de 144
98
Audio Command Center Series Manual — P/N 51889:E1  6/8/2010
Section 6: Power Supply Calculations
6.1  Overview
This section contains instructions and tables for calculating power supply currents in alarm and 
standby conditions.  This is a four-step process, consisting of the following:
1. Calculating the total amount of AC branch circuit current required to operate the system
2. Calculating the power supply load current for non-fire and fire alarm conditions and 
calculating the secondary (battery) load
3. Calculating the size of batteries required to support the system if an AC power loss occurs
4. Selecting the proper batteries for your system
6.2  Calculating the AC Branch Circuit
The audio distribution panel requires connection to a separate, dedicated AC branch circuit, which 
must be labeled FIRE ALARM.  This branch circuit must connect to the line side of the main 
power feed of the protected premises.  No other non-fire alarm equipment may be powered from 
the fire alarm branch circuit.  The branch circuit wire must run continuously, without any discon-
nect devices, from the power source to the transponder.  Overcurrent protection for this circuit must 
comply with Article 760 of the National Electrical Codes as well as local codes.  Use 14 AWG 
(2.00 mm
2
) wire with 600 volt insulation for this branch circuit.
The ACC-25/50, ACC-25/50ZS and ACC-25/50ZST require 1.5 amps from the AC branch circuit.
6.3  Calculating the System Current Draw
6.3.1  Overview
The secondary power source (batteries) must be able to power the system during a primary power 
loss.  To calculate the non-fire alarm load on the secondary power source, use Calculation 
Column 1 in Table 6.3 .  The ACC-25/50 must support a larger load current during a fire alarm con-
dition and primary power loss.  To calculate the fire alarm load on the secondary power source, use 
Calculation Column 2 in Table 6.3 .
When calculating current draw and the battery size, note the following:
‘Primary’ indicates that the audio panel is being powered by AC
‘Secondary’ indicates that the audio panel is being powered by battery backup during AC 
failure
All currents are given in amperes (A) and refer to the DC current being supplied by the panel.  
Table 6.1 shows how to convert milliamperes and microamperes to full amperes 
To convert....
Multiply
Example
Milliamperes (mA) to
amperes (A)
mA x 0.001
3 mA x 0.001 = 0.003 A
Microamperes (µA) to
amperes (A)
µA x 0.000001
300 µA x 0.000001 = 0.0003 A
Table 6.1  Converting to Full Amperes