Emerson IFT9701 Manuel D’Utilisation

Page de 90
60
Model IFT9701 Transmitter Instruction Manual
Troubleshooting
 continued
Figure 8-2
Power supply connections
7. Make sure the power cable is not installed in the same conduit or cable tray as output wiring.
8. Make sure the meter is properly grounded. If national standards are not in effect, adhere to this 
standard:
For grounding, use copper wire, 14 AWG (2,5 mm²) or larger wire size.
Either the internal ground screw or external case ground screw may be used as required by 
local policy or code.
Keep all ground leads as short as possible.
Flowmeter must be grounded with less than 1 ohm impedance.
Connect power-supply ground directly to earth.
The flowmeter does not have replaceable fuses for the power supply.
8.5
Wiring
For detailed wiring instructions, refer to Chapters 3 and 4.
Wiring problems are often incorrectly diagnosed as a faulty sensor. At initial startup of the 
transmitter, always check the following:
1. Proper cabling, and use of shielded pairs
2. Proper wire termination
Wires on correct terminals.
Wires making good connections with the terminal strip.
Wires making good connections at the receiving device.
Wires making good connections at the sensor terminals. Table 8-3 lists terminal 
designations for Micro Motion sensors.
¾-inch NPT or M20
conduit opening
Seal opening with
conduit seal or
cable gland
Power supply 
terminals
Internal ground
screw
External case
ground screw
Voltage label
Match power supply to 
voltage specified on label