A.O. Smith 197835-001 Manuel D’Utilisation

Page de 44
21
InstallatIon sequence
For installations in the City of Los Angeles, California Category IV
PVC Pipe such as that manufactured by Brownline Pipe Company,
must be used as vent pipe material.
 
cautIon
vent terMInals supplIed wIth heater Must Be used.
NOTE:  BEFORE  BEGINNING  INSTALLATION  OF  ANY 
VENT  PIPE  READ  THE  VENT  PIPE  MANUFACTURER’S
INSTALLATION INSTRUCTIONS.
1.  After  the  points  of  termination  have  been  determined, 
use  the  cover  plates  as  templates  to  mark  the  holes  for 
the vent pipes to be inserted through the wall. BEWARE OF
CONCEALED WIRING AND PIPING INSIDE OF WALL. If the 
vent terminals are being installed on the outside of a finished
wall,  it  may  be  easier  to  mark  both  the  inside  and  outside
wall. Align the holesby drilling a hole through the center of the
template from the inside through to the outside. The template
can now be positioned on the outside wall using the drilled holes
as a centering point for the template.
    A.)  MASONRY  SIDE WALLS  Chisel  an  opening  approximately 
   
1/2” (1.3 cm) larger than the marked circle.
   B.)  WOODEN SIDE WALLS Drill a pilot hole approximately 
   
one  quarter  inch  outside  of  the  marked  circle.  This 
   
pilot  hole  is  used  as  a  starting  point  for  a  saws-all  or 
   
sabre saw blade. Cut around the marked circle staying 
   
approximately  one  quarter  inch  outside  of  the  line. 
   
(This  will  allow  the  vent  pipe  to  easily  slide  through 
   
the  opening. The  resulting  gap  will  be  covered  by  the 
   
vent  terminal  cover  plates.)  Repeat  this  step  on  the 
     
inside wall if necessary.
2.  Cut a length of 3” PVC pipe about 3.5” (8.9 cm) longer than the 
 wall thickness at the opening.
3.  Glue the intake vent terminal to the section of the pipe.
4.  Slide the wall plate over pipe to stop against intake vent terminal.
5.  Place a bead of caulking (not supplied) around the gap between 
 the  pipe  and  the  wall.  Place  some  of  the  caulking  on  the 
 back of the plate to hold it against the wall after installation.
6.  If the vent pipe is installed up to the wall, with a coupling on the 
 end against the wall opening, the pipe with the vent terminal can 
 be prepared for gluing before inserting through the wall. Slide the 
 pipe through the wall and insert into coupling on the other side of 
 the wall, making sure that the vent terminal ends up pointed in the 
 correct position (Figure 19).
FIGURE 19.
vertIcal vent terMInal InstallatIon
 
IMportant
when terMInatInG throuGh a roof, the followInG 
specIfIcatIons  pertaInInG  to  terMInal  locatIon 
Must Be followed.
1.  Proper support must be provided for all pipe protruding through 
  the roof.
2.  The vertical roof terminations should be sealed with a plumbing 
 roof boot or equivalent flashing.
3.  The intake vent termination and the exhaust vent termination must 
 penetrate the same side of roof.
4.  The center line of the intake vent termination and the center 
 line  of  the  exhaust  vent  termination  must  be  no  closer 
 than 24” (61cm).
5.  The intake vent terminal and the exhaust vent terminal must be 
 oriented facing downward and the same direction.
The specifications are displayed in Figures 20 & 21.
NOTE:  Exhaust  vent  terminal  is  installed  using  the  same
procedure.
FIGURE 20.
FIGURE 21.