Emerson 1F97-1277 Manuel De Montage

Page de 12
2
2 "AA" Batteries
WIRING CONNECTIONS 
Refer to equipment manufacturers' instructions for specific 
system wiring information . After wiring, see CONFIGURA-
TION section for proper thermostat configuration.
For wiring diagrams, see next page .
Wiring diagrams shown are for typical systems and describe 
the thermostat terminal functions .
INSTALLATION 
Battery Location
2 "AA" alkaline batteries are included in the thermostat at 
the factory with a battery tag to prevent power drainage . 
Remove the battery tag to engage the batteries .
To replace batteries, set system to OFF, remove thermostat 
from wall and install the batteries in the rear along the top of 
the thermostat (see Figure 1) .
Remove Old Thermostat
A standard heat/cool thermostat consists of three basic parts:
1 .  The cover, which may be either a snap-on or hinge type .
2 .  The base, which is removed by loosening all captive 
screws .
3 .  The switching subbase, which is removed by unscrewing
  the mounting screws that hold it on the wall or adapter
 plate . 
Before removing wires from old thermostat,
  label each wire with the terminal designation from
  which it was attached. Disconnect the wires from the old 
thermostat one at a time . 
Do not let wires fall back into 
the wall.
Installing New Thermostat
1 .  Pull the thermostat body off the thermostat base . Forcing
  or prying on the thermostat will cause damage to the unit .
2 .  Place base over hole in wall and mark mounting hole 
  locations on wall using base as a template .
3 .  Move base out of the way . Drill mounting holes . If you
  are using existing mounting holes and the holes drilled
  are too large and do not allow you to tighten base snugly, 
use plastic screw anchors to secure the base .
4 .  Fasten base snugly to wall using mounting holes shown
  in Figure 1 and two mounting screws . Leveling is for
  appearance only and will not affect thermostat operation .
5 .  Connect wires to terminal block on base using appropriate 
wiring schematic (see diagrams on next page) .
6.  Push excess wire into wall and plug hole with a fire resis-
tant material (such as fiberglass insulation) to prevent
  drafts from affecting thermostat operation .
7 .  Carefully line the thermostat up with the base and snap
  into place .
  Terminal Designation 
Description
 B   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Changeover valve for heat pump energized constantly in heating
 O   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Changeover valve for heat pump energized constantly in cooling
 Y   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Compressor Relay
 G   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Fan Relay
 RC .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Power for Cooling
 RH .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Power for Heating
 C   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Common wire from secondary side of cooling 
 L   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . For Call for Service indicator for systems with diagnostic connection
 6   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Powered closed connection for 3-wire zone valve
 W   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Heat Relay
 - .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Common (DC) for wired remote temperature sensor
 S   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Frequency signal from remote temperature sensor
 +   .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  .  . Power (DC) to remote temperature sensor
TERMINAL DESIGNATION DESCRIPTIONS
Mounting
Hole
Mounting
Hole
Place Level
across
Mounting Tabs
(for appearance only)
Place Level
across
Mounting Tabs
(for appearance only)
+
S
-
W/E
6
L
Figure 1 – Thermostat Base Multi-Stage 1F97-1277
Rear view of thermostat
WARNING
!
Thermostat installation and all components of the 
control system shall conform to Class II circuits per 
the NEC code.