To enter the menu: Press the 
Menu touch key . Press and hold for 5 seconds the Installer Config touch key . This displays 
menu item #1 in the table below . Press   to advance to the next menu item or   to return to a previous menu item . Press   
or   to change a menu item .
Installer Note: To default the programming, clock and Configuration Menu to the Factory Default Settings, press the  ,   
and SYSTEM keys simultaneously . The thermostat display will go blank for a few seconds, and then all segments will display 
momentarily . 
For heat pump systems, Configuration Menu item 1 must be set to match the heat pump system. 
If first item does not show SS1 or HP1, you have an earlier thermostat model and need Instruction Sheet 37-6814D.
CONFIGURATION MENU
Menu
Reference
Number
Program-
mable
Non-
Program-
mable
Press 
Button
Displayed 
(Factory 
Default)
Press    or   to 
select from listed 
options
Comments
1
1
1
SS1
HP1, SS1
Selects Single Stage or Heat Pump
 (1  compressor)
2
2
2
(ELE)
GAS
GAS setting: furnace controls blower
ELE setting: thermostat controls blower
3
3
3
Days, 
(7) P
5+1+1 or 0
Programs per week . (0 = non-programmable)
4
4
NA
PS (4)
2
Program periods per day
4 = Morning, Day, Evening, Night
2 = Day, Night
5
5
4
Cool-Off-
Heat-Auto
Cool-Off-Heat,
Off-Heat, Cool-Off
System switch configuration in single stage
Cool-Off-Heat-
Emer-Auto
Cool-Off-Heat-Emer,
Off-Heat-Emer, 
Cool-Off
System switch configuration, heat pump mode
6
6
NA
(On)
OFF
Selects Energy Management Recovery, E (with programming option on)
7
7
5
Cr, Heat (FA)
SL
Selects Adjustable Anticipation, cycle rate, Heat
8
8
6
Cr, Cool (FA)
SL
Selects Adjustable Anticipation, cycle rate, Cool
9
9
7
Cr/AU, Emer (FA)
SL
Selects Adjustable Anticipation, cycle rate auxiliary, (This item is
only to appear if HP1 is selected above)
10
10
8
CL (OFF) 
On
Selects Compressor Lockout
11
11
9
dL (On)
OFF
Selects Continuous Display backlight & intensity
12
12
10
dL (LO)
HI
Selects Backlight Intensity
13
13
11
0
4, LO to 4, HI
Selects Adjustable Ambient Temperature Display [range -4 (LO) 
to +4 (HI)]
14
14
12
°F
°C
Selects °F/°C Display (temperature units in Fahrenheit or Celsius) .
15
15
13
b (On)
OFF
Selects audible Beeper On/Off
16
16
14
dS (On)
OFF
Selects Daylight Saving Time calculation
17
17
15
AS, Heat (On)
OFF
Selects Automatic Schedule for comfort temperature Programming,
heat mode
18
18
16
AS, Cool (On)
OFF
Selects Automatic Schedule for comfort temperature Programming, 
cool mode
19
19
17
CS, (OFF)
Cool Savings
1-2-3-4-5-6
Selects Cool Saving Feature & amount
20
20
18
HL, Heat (99)
62-98
TEMPERATURE LIMIT, HEAT (max . heat set point)
21
21
19
LL, Cool (45)
46-82
TEMPERATURE LIMIT, COOL (min . cool set point)
22
22
20
OFF, 
Keypad Lockout
L (total), P (partial),
Temperature Limit
(limited temperature 
range)
Selects Keypad Lockout
000
001-999
Selects Keypad Lockout Combination (active only if keypad Lockout 
is selected) .
23
23
21
FS, Heat (On)
OFF
Fast second stage of heat (not available if SS1 is selected above)
24
24
22
Remote (OFF)
On
Remote temperature sensor, enable/disable
In, Remote
Outdoor Remote
Remote temperature sensor (Indoor/Outdoor)
LS (On)
OFF
Local temp . Sensor enable/disable (only when Indoor Remote is 
selected On) .
25
25
23
dF (5)
5-50
Selects Dual Fuel Feature & set point (in Fahrenheit) 
(applicable only when HP1 is selected)
Cd (60)
0-99
Selects Compressor delay in seconds (only when 
dF is selected >5)
26
26
24
Change Filter
(OFF)
On
Selects Change filter feature
200 Hours
25-1975 
(in increments
of 25 hours)
Change filter, duration hours
 
 INSTALLER/CONFIGURATION MENU