SITRANS LU01 – INSTRUCTION MANUAL
7ML19985BE02
Pa
ra
m
e
te
rs
mA Output Failsafe (P219) 
P219 mA Output Failsafe 
Use for failsafe operation, independent of the Failsafe Material Level (P071).
Selecting an independent mA Failsafe option: 
1.
Press MODE 
 to display the Auxiliary Function symbol. 
2.
Press ARROWS 
 
 to scroll access the failsafe options. 
3.
Press ENTER 
 when the desired option displayed.
Or, to produce an mA output at a specific value, enter the value required. This is used only 
if mA output is allocated to a transducer (P201 = 1 to 4).
Standard Data Logging (P300 to P321) 
All records can be reset by pressing the CLEAR 
 keys.
Record Temperatures (P300 to P303) 
These features display the high and/or low temperatures in °C. When a parameter 
relating to a TS-3 Temperature Sensor is accessed, the Index Type display changes to the 
TS-3 symbol  .
If the unit is powered up without a temperature sensor connected, the value –50 °C is 
displayed. This information can help trace problems with both built in and external 
temperature sensors.
P300 Temperature, Transducer Maximum
Shows the highest temperature encountered, as measured by the temperature sensor in 
the transducer (if applicable).
Press CLEAR 
 keys to reset the log after a short circuit on the transducer wiring.
Primary Index
mA output
Values
Range: 0.000 to 22.00
OFF
*
mA output responds to Failsafe Material Level (P071).
HOLd
last known value is held until normal operation 
resumes
LO
produce the Empty mA output immediately
HI
produce the Span mA output immediately
Related
P201 mA Output Function
Values
Range: - 50 to 150°C (view only)
Preset: - 50°C