GE 23954 Manuel D’Utilisation

Page de 58
2.2  COMMAND LIST 
The various commands are split in different groups, depending on the involved functionality, and are 
listed here in accordance with their group classification.  
The command-line interface includes a command auto-completion feature. Normally, typing a 
command without any parameter displays usage information on the command. A help command is 
also available. 
Note that all commands are case-sensitive. 
 
 
2.2.1  General command group 
The general command group consists of the following commands: 
 
Command Parameters 
Description 
help 
general | network | dns | 
user | service |  
time  | smtp | snmp | 
trap | ups | rccmd | 
events | log  
Show help information 
general   shows all general commands 
network  shows all network commands 
etc … 
list 
 
List all available commands 
version 
 
Display the board FW version 
logout 
 
User logout 
NOTEAuto-logout after 10 min inactivity 
exit 
 User 
logout 
Change current user password 
passwd 
 
NOTEPassword length is limited to 8 chars.  
The command line interface may accept longer passwords, although 
only the first 8 characters are significant. 
ping 
[hostname] | [X.X.X.X] 
Ping IP address or hostname 
hostname fully 
qualified 
hostname 
X.X.X.X IP-address 
nvdefault 
 
Reset the configuration to factory default 
nvsave 
 
Save changes to non-volatile memory 
nvdump 
 
Dump configuration file (gedeups.cfg) to FTP area  
Update the SNMP/Web configuration with the gedeups.cfg file from 
the FTP area 
 
nvupdate 
NOTEThe adapter performs no checks on the received file. Make sure 
the file format is correct - unexpected behaviour may occur. 
upgrade 
Start the upgrade with the uploaded firmware 
NOTEFW file to be uploaded via FTP 
 
reboot 
 
System restart (soft-reset) 
NOTEAll unsaved changes will be lost 
Modifications reserved 
Page 14/58 
OPM_CNT_SNM_BAS_CRD_1GB_V012.doc 
Operating Manual SNMP/Web Adapter