2.2.10  UPS command group 
The UPS command group allows monitoring and configuration of the managed UPS system. 
 
Command Parameters 
Description 
upsinfo  
(*) 
Show detailed UPS information  
upstest  
(*) 
Start/Stop UPS tests 
upscontrol  
(*) 
Control the UPS (1-ph/SP versions ONLY
upsconfig   
(*) 
Configure UPS parameters 
attacheddevice  [device] 
Set UPS attached device 
[device] 
Device which is powered/protected by the UPS 
NOTE:  Maximum length 63 chars. If this parameter contain 
blanks or special characters it shall be specified in between 
double quotation marks (“...”)
  
alarmdelay  
[time] 
Set alarm delay time (1-ph/SP version ONLY
[time]  Time in seconds before alarm notification  
NOTEThis parameters is factory set to its ideal value and 
shall not be changed unless instructed to do so
 
retrydelay  
[time] 
Set retry delay time (1-ph/SP version ONLY
[time]  Time in seconds between re-connection attempts 
NOTEThis parameters is factory set to its ideal value and 
shall not be changed unless instructed to do so
 
retrycount  
[count] 
Set retry count (1-ph/SP version ONLY
[count] Number of re-connection attempts 
NOTEThis parameters is factory set to its ideal value and 
shall not be changed unless instructed to do so
 
serialbypass 
on | off 
Enable/disable the serialbypass functionality 
NOTEThis command is offered for UPS service access ONLY. 
It use outside of this scope is not recommended (enabling 
this functionality stops the UPS monitoring
 
Show/Set card address on the IMV bus 
[address] 
Card address in the range 0, 54-57  
NOTEThis setting may overrides the HW setting through the 
dip-switches on the card. Setting this parameter to 0 reverts 
to the HW settings. 
This setting becomes active only after reboot (save the 
settings!)
 
[address] 
cardaddress 
Enable/disable write commands to the UPS 
Setting  readonlymode to on will stop any write operation 
towards the UPS (the SNMP/Web adapter will effectively 
switch to read-only mode). The UPS Test, Control and Config 
web pages will not be shown in the navigator bar. 
[on | off]  
readonlymode 
Caution! Once enabled, this setting may not be reverted. 
NOTE1-ph/SP versions ONLY 
Modifications reserved 
Page 23/58 
OPM_CNT_SNM_BAS_CRD_1GB_V012.doc 
Operating Manual SNMP/Web Adapter