(*) By running these commands, an interactive menu is launched – follow the on-screen instructions. 
The menu also provide a complete on-line help section. 
 
NOTE: When using the local serial connection, make sure that the terminal emulation is set to VT-100, 
otherwise the interactive menu may not be rendered correctly. 
 
Caution! Some of these commands (particularly upscontrol and upsconfig) may inject commands 
and/or alter the UPS configuration with consequences on the UPS operation that may affect the load.  
Make sure you fully understand the effect on the UPS and on the load before injecting any of these 
commands. Make sure that it is safe to perform the desired operation for both the UPS and the load. 
 
 
 
 
 
2.2.11  Rccmd command group 
The  rccmd command group allows to configure the RCCMD Server embedded in the SNMP/Web 
adapter.  
 
 
Command Sub-command Parameters 
Description 
showrccmd 
 
 
Shows the current RCCMD Server 
configuration 
 
Enable/disable Network Shutdown function 
on|off 
on  
Network Shutdown enabled 
off  
Network Shutdown disabled) 
add 
Add an RCCMD Client  
[ip] 
IP-address of the trap target 
[port]  Port on which the client is listening 
[cond] Shutdown condition: 
 
aXX 
after XX minutes on battery 
 
bXX 
at XX min remain batt time 
[ip]  
[port]  
[cond] 
rccmd 
Send an RCCMD test message to a specific 
RCCMD client 
[num] 
test 
[row]  RCCMD client reference 
Delete an RCCMD Client  
[row]  RCCMD client reference 
[num] 
del  
 
 
 
 
Modifications reserved 
Page 24/58 
OPM_CNT_SNM_BAS_CRD_1GB_V012.doc 
Operating Manual SNMP/Web Adapter