Emerson MONITORING OpenComms Manuel D’Utilisation

Page de 56
Modbus Communications and Connectivity
21
Figure 7
Exceeding maximum specifications
The maximum specification may be exceeded if measures are taken to 
drive or boost the EIA-485 communication line. Two wire EIA485 
repeaters are available through the Liebert Corporation. SiteScan’s 
“REPOPT” will work sufficiently for this application. Consult the 
SiteScan price book for pricing schedule and alternative solutions.
5.4
Modbus Slave Functions
5.4.1 Data Type
The OpenComms NIC supports data in a register block as one of the 
following types: Signed integer (16 bit) / Unsigned integer (16 bit) / 
Signed long (32 bit); IEEE floating-point (32 bit); Null terminated 
String.
A datum should consist of one or multiple registers. The leftmost byte 
contains the MSB and the rightmost byte contains the LSB.
Modbus RTU Master
EIA-485 9600,N,8,1
Maximum of 32 
devices with combine 
cable length of 4000 
feet
Modbus RTU Master
EIA-485 9600,N,8,1
Maximum of 32 
devices with combine 
cable length of 4000 
feet
R
R